GUIDE SPECIFICATIONS
PACKAGED TERMINAL COOLING UNIT WITH HEAT PUMP OR ELECTRIC HEATING
HVAC Guide Specifications
Size Range: Cooling: 6,900 to 15,100 Btuh Heating: 6,000 to 14,100 Btuh Heat Pump
6,400 to 17,000 Btuh Electric Carrier Model Numbers:
52PC Premier Series, Cooling Only
52PE Premier Series, Cooling with Electric Heat
52PQ Premier Series, Heat Pump with Electric Heat
52CE Comfort Series, Cooling with Electric Heat
52CQ Comfort Series, Heat Pump with Electric Heat
Part 1 — General
1.01 SYSTEM DESCRIPTION
Single piece,
A.Insulated Polymer Wall Sleeve:
Wall sleeve shall provide excellent thermal insula- tion, be textured to hide scratches and prevent shine, will have superior outdoor noise absorption and shall be corrosion free for the life of the prod- uct. The Wall Sleeve must have dimensions of
42 in. width x 16 in. height x 147/8 in. depth and be shipped with a rear weather barrier installed.
B.Wall Sleeve Molding:
Molding shall trim the wall sleeve to the existing wall, to hide wall imperfections and irregularities in the wall opening.
C.Outdoor Polymer Louvered Grille:
Outdoor grille shall resist corrosion, breakage and match the color specified on drawing schedule and specifications.
D.Subbase:
Subbase will support the wall sleeve when it extends into the room more than 4 inches. Subbase must come from the factory
1.02 QUALITY ASSURANCE
System shall be approved and certified by UL and UL, Canada. Chassis capacity and efficiency perfor- mance shall be certified in accordance with ARI standard 310/380. Chassis shall meet ASHRAE Standard 90.1 for minimum energy efficiency.
Chassis shall meet the New York City Department of Building, Material and Equipment acceptance require- ment (MEA).
1.03DELIVERY, STORAGE, AND HANDLING
A.The packaging of the chassis shall be sufficient to protect the chassis from damage during shipment via an enclosed truck. Chassis must also be able to withstand an impact force of 10 g’s and a random continuous force of 1g, during shipping.
B.Chassis, wall sleeves, and grilles shall be shipped in separate cartons. Universal handling instructions shall be defined and visible on the carton, from front, back and sides.
C.Chassis shall be capable of withstanding tempera- tures from
D.Unit shall be stored and handled per manufacturer’s recommendations.
Part 2 — Products
2.01EQUIPMENT
A.General:
Packaged Terminal Air Conditioners shall be of the sizes and capacities as shown on the contract draw- ing schedule and in the specifications.
B.Chassis:
The chassis shall be a
1.Operating Characteristics:
Chassis shall be capable of starting and run- ning at 115 F ambient outdoor temperature per maximum load criteria of ARI Standard 310/ 380.
2.Electrical:
Chassis shall be equipped with a 58 in. power cord for 208/230 v models or a 15 in. power cord for 265 v models. The chassis current draw shall be specified on the chassis name- plate and match electrical requirements speci- fied on the Contract drawing schedule and specifications. The power cord plug configura- tion shall conform to NEMA standards and the rating shall support the current draw of the electric resistance heater.
For 265 v installations, UL codes require the use of an electrical equipped subbase for power cord usage or hardwire conduit for non- corded installations.
C.Airflow System:
The airflow system shall consist of one permanent
51