Carrier P5030-100 installation instructions A - Physical Data 48P2,P3,P4,P5030-050cont

Models: P4 48P2 P3 P5030-100

1 76
Download 76 pages 26.42 Kb
Page 4
Image 4

Table 1A — Physical Data 48P2,P3,P4,P5030-050 (cont)

BASE UNIT

 

48P2,P3,P4,P5040

 

 

 

 

 

48P2,P3,P4,P5050

NOMINAL CAPACITY (tons)

 

 

 

40

 

 

 

 

 

 

 

50

 

 

OPERATING WEIGHT (lb)

 

Standard Chassis

 

 

Extended Chassis

 

 

 

Standard Chassis

 

 

Extended Chassis

Base Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat

 

5810

 

 

 

 

6310

 

 

 

6025

 

 

6525

High Heat

 

5940

 

 

 

 

6440

 

 

 

6155

 

 

6655

With Economizer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat

 

6110

 

 

 

 

6610

 

 

 

6325

 

 

6825

High Heat

 

6240

 

 

 

 

6740

 

 

 

6455

 

 

6955

COMPRESSORS

 

 

 

 

 

 

 

 

Scroll

 

 

 

 

Quantity...Type

 

2...ZP103/1...ZP182

 

 

 

 

 

2...ZP120/2...ZP137

 

 

 

 

 

 

Oil Charge (oz) per Compressor

 

 

 

110

 

 

 

 

 

 

 

110

 

 

Number of Refrigerant Circuits

 

 

 

2

 

 

 

 

 

 

 

 

2

 

 

REFRIGERANT

 

 

 

 

 

 

 

 

R-410A

 

 

 

 

Operating Charge (lb), Ckt 1/Ckt 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Evaporator Coil

 

 

 

21.6/26.7

 

 

 

 

 

 

 

29.4/29.0

 

 

 

 

 

 

 

 

 

 

Standard Evaporator with Humidi-MiZer®

 

 

 

21.6/39.1

 

 

 

 

 

 

 

29.4/41.4

Alternate High-Capacity Evaporator Coil

 

 

 

35.1/37.2

 

 

 

 

 

 

 

38.2/36.5

Alternate High-Capacity Evaporator with Humidi-MiZer

 

 

31.1/49.6

 

 

 

 

 

 

 

38.2/48.9

CONDENSER COILS

 

 

 

Aluminum Novation® Heat Exchanger with Microchannel Coils

 

 

Quantity

 

 

 

2

 

 

 

 

 

 

 

 

2

 

 

Total Face Area (sq ft)

 

 

 

66.7

 

 

 

 

 

 

 

66.7

 

EVAPORATOR COILS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity

 

 

 

 

 

 

 

 

1

 

 

 

 

 

Total Face Area (sq ft)

 

 

 

 

 

 

 

 

45.5

 

 

 

 

 

Refrigerant Feed Device...No. per Circuit

 

 

 

 

 

 

 

 

TXV...2

 

 

 

 

Standard Evaporator Coils

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

 

 

3...15.0

 

 

 

 

 

 

 

4...15.0

 

Fin Type

 

 

Double Wavy

 

 

 

 

 

 

 

Double Wavy

Tube Type

 

 

Cross Hatched

 

 

 

 

 

 

 

Cross Hatched

Alternate, High-Capacity Evaporator Coils

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

 

 

6...16.0

 

 

 

 

 

 

 

6...16.0

 

Fin Type

 

 

Double Wavy

 

 

 

 

 

 

 

Double Wavy

Tube Type

 

 

Cross Hatched

 

 

 

 

 

 

 

Cross Hatched

HEATING SECTION

 

Low Heat

 

 

 

 

High Heat

 

 

 

Low Heat

 

 

High Heat

Number of Heat Exchangers

 

7

 

 

 

 

14

 

 

 

7

 

 

 

14

Input (MBtuh)

 

325

 

 

 

 

650

 

 

 

325

 

 

650

Output (MBtuh) (Vertical/Horizontal)

 

263/260

 

 

 

 

527/520

 

 

 

263/260

 

527/520

Temperature Rise Range (F)

 

10-40

 

 

 

 

25-55

 

 

 

10-40

 

 

25-55

Efficiency (%) (Vertical/Horizontal)

 

81/80

 

 

 

 

81/80

 

 

 

81/80

 

 

81/80

Burner Orifice Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity (in. ...drill no.)

 

7 (.1285...30)

 

 

 

 

14 (.1285...30)

 

 

 

7 (.1285...30)

 

14 (.1285...30)

Manifold Pressure (in. wg)

 

3.5

 

 

 

 

3.5

 

 

 

3.5

 

 

 

3.5

Line Pressure (in. wg) (min...max)

 

5.0...13.0

 

 

 

 

5.0...13.0

 

 

 

5.0...13.0

 

5.0...13.0

Firing Stages

 

2

 

 

 

 

2

 

 

 

2

 

 

 

2

Number of Gas Valves

 

1

 

 

 

 

2

 

 

 

1

 

 

 

2

CONDENSER FANS

 

 

 

 

 

 

 

Propeller Type

 

 

 

 

Quantity...Diameter (in.)

 

 

 

3...30

 

 

 

 

 

 

 

4...30

 

Nominal Cfm

 

 

 

30,000

 

 

 

 

 

 

 

38,000

 

Motor Hp...Rpm

 

 

 

1.0...1140

 

 

 

 

 

 

 

1.0...1140

SUPPLY FAN

 

 

 

 

 

 

 

Centrifugal 25 x 25 in.

 

 

 

 

Nominal Cfm

 

 

 

14,000

 

 

 

 

 

 

 

14,000

 

 

 

 

 

 

 

 

 

 

 

Maximum Allowable Cfm

 

 

 

20,000

 

 

 

 

 

 

 

20,000

 

Maximum Allowable Rpm

 

 

 

900

 

 

 

 

 

 

 

900

 

Shaft Diameter at Pulley (in.)

 

 

 

111/16

 

 

 

 

 

 

 

111/16

 

SUPPLY-FAN MOTOR AND DRIVE

 

 

 

 

 

 

 

(Any motor available on any unit)

 

 

 

 

Motor Hp

 

7.5

 

10

 

15

20

 

25

 

30*

Motor Frame Size

 

213T

 

215T

 

254T

 

 

 

256T

 

284T

 

286T

Efficiency at Full Load (%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Efficiency

 

88.5

 

89.5

 

91.0

 

91.0

 

91.7

 

 

92.4

Premium Efficiency

 

91.7

 

91.7

 

93.0

 

93.6

 

93.6

 

 

93.6

Fan Pulley Pitch Diameter (in.)

 

13.7

 

13.7

 

13.7

 

13.7

 

13.7

 

 

12.5

Motor Pulley Pitch Diameter (in.)

 

3.4

 

4.3

 

4.9

 

5.5

 

6.5

 

 

6.5

Resulting Fan Speed (rpm)

 

438

 

549

 

626

 

703

 

830

 

 

910

Belts Quantity...Type

 

2...BX60

 

2...5VX630

 

2...5VX630

 

 

 

2...5VX630

 

2...5VX650

 

3...5VX630

Center Distance Range (in.)

 

17.74-14.30

 

17.74-14.30

 

17.63...14.01

 

17.63...14.01

 

16.63...12.87

 

16.63...12.87

OPTIONAL POWER EXHAUST†

 

 

 

 

 

Centrifugal, 18 x 15 in. (Any motor available

on any unit)

 

 

Quantity...Motor Hp

 

2...3.0

 

 

 

 

2...5.0

 

 

 

2...7.5

 

 

2...10

 

 

 

 

 

 

 

Motor Frame Size

High Eff

56HZ

 

 

 

 

184T

 

 

 

213T

 

 

 

215T

Efficiency at Full Load (%) High/Premium

Prem Eff

182T

 

 

 

 

184T

 

 

 

213T

 

 

 

215T

 

81.0/88.5

 

 

 

 

87.5/89.5

 

 

 

88.5/91.7

 

89.5/91.7

Fan Pulley Pitch Diameter (in.)

High Eff

11

 

 

 

 

10.4

 

 

 

12

 

 

 

12

 

Prem Eff

11.0

 

 

 

 

10.4

 

 

 

12

 

 

 

12

Motor Pulley Pitch Diameter Range (in.)

High Eff

4.1-3.1

 

 

 

 

4.7-3.7

 

 

 

6.0-4.8

 

 

7.0-5.8

Motor Pulley Pitch Diameter Factory Setup (in.)

Prem Eff

4.1-3.1

 

 

 

 

4.7-3.7

 

 

 

6.0-4.8

 

 

7.0-5.8

 

4.1

 

 

 

 

4.2

 

 

 

5.4

 

 

 

6.4

Blower Shaft Diameter at Pulley (in.)

 

17/16

 

 

 

 

17/16

 

 

 

17/16

 

 

17/16

Fan Rpm Range

 

500-656

 

 

 

 

621-785

 

 

 

717-882

 

854-1000

Factory Setup Fan Rpm

 

656

 

 

 

 

703

 

 

 

800

 

 

927

Maximum Allowable Rpm

 

1000

 

 

 

 

1000

 

 

 

1000

 

 

1000

FILTERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Efficiency Throwaway (Standard)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

8...20 x 25 x 2, 8...20 x 20 x 2

 

 

 

8...20 x 25 x 2, 8...20 x 20 x 2

Medium Efficiency (30%) Pleated (Optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

8...20 x 25 x 2, 8...20 x 20 x 2

 

 

 

8...20 x 25 x 2, 8...20 x 20 x 2

High Efficiency (90%) Bag Filters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with High Velocity Prefilters (Opt)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bag Filter

 

6...20 x 24 x 22,

6...20 x 20 x 22

 

 

 

6...20 x 24 x 22, 6...20 x 20 x 22

Prefilter

 

12...16 x 20 x 2,

3...20 x 24 x 2

 

 

 

12...16 x 20 x 2,

3...20 x 24 x 2

MERV 15 Cartridge Filters with High Velocity Prefilters (Opt)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity...Size (in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cartridge Filter

 

6...20 x 24 x 12, 6...20 x 20 x 12

 

 

 

6...20 x 24 x 12, 6...20 x 20 x 12

Prefilter

 

12...16 x 20 x 2, 3...20 x 24 x 2

 

 

 

12...16 x 20 x 2, 3...20 x 24 x 2

OUTSIDE AIR SCREENS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Hood (25%) Quantity...Size (in.)

 

 

 

None

 

 

 

 

 

 

 

None

OPTIONAL ECONOMIZER FILTER

 

 

5...20 x 20 x 2

 

Aluminum Frame, Permanent

5...20 x 20 x 1

Quantity...Size (in.)

 

 

 

 

 

 

 

 

 

 

 

2...20 x 25 x 1

 

 

 

 

 

 

 

2...20 x 25 x 1

 

 

 

 

 

 

 

 

 

 

LEGEND

* 460-3-60 only.

MBtuh — Btuh in Thousands

†See Table 7 — Power Exhaust Fan Drive Data on page 9 for more information.

TXV — Thermostatic Expansion Valve

 