Carrier P3, P5030-100, 48P2, P4 installation instructions Voltage

Models: P4 48P2 P3 P5030-100

1 76
Download 76 pages 26.42 Kb
Page 41
Image 41
Manual background

Table 11 — Electrical Data, 48P2,P3,P4,P5035 Units (cont)

 

VOLTAGE

 

COMPRESSOR

 

CONDENSER

EVAPORATOR FAN

 

POWER EXHAUST

POWER SUPPLY

VOLTAGE

RANGE

 

No. A1

 

 

No. B1

 

FAN MOTOR

 

MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

3 PH,

Min

Max

Qty

RLA

 

LRA

Qty

RLA

 

LRA

Qty

FLA

Hp

FLA

Qty

Hp

FLA

MCA

FUSE OR

60 Hz

(ea)

 

(ea)

(ea)

 

(ea)

(ea)

(ea)

HACR BRKR*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67.5

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

3.9

75.3

90

 

 

 

 

 

 

 

 

 

 

 

 

 

7 1/2

9.0

2

 

5

6.1

79.7

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

7.5

9.0

85.5

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

10

11.0

89.5

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

69.5

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

3.9

77.3

100

 

 

 

 

 

 

 

 

 

 

 

 

 

10

11.0

2

 

5

6.1

81.7

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

7.5

9.0

87.5

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

10

11.0

91.5

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75.5

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

3.9

83.3

100

 

 

 

 

 

 

 

 

 

 

 

 

 

15

17.0

2

 

5

6.1

87.7

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

7.5

9.0

93.5

110

575

518

632

1

23.7

 

132

1

23.7

 

132

2

2.6

 

 

2

 

10

11.0

97.5

110

 

 

(ea)

 

 

 

80.5

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

3.9

88.3

110

 

 

 

 

 

 

 

 

 

 

 

 

 

20

22.0

2

 

5

6.1

92.7

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

7.5

9.0

98.5

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

10

11.0

102.5

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86.4

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

3.9

94.2

110

 

 

 

 

 

 

 

 

 

 

 

 

 

25

27.0

2

 

5

6.1

98.6

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

7.5

9.0

104.4

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

10

11.0

108.4

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

92.6

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

3

3.9

100.4

125

 

 

 

 

 

 

 

 

 

 

 

 

 

30

32.0

2

 

5

6.1

104.8

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

7.5

9.0

110.6

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

10

11.0

114.6

125

 

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning, and Refrigeration

Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

RLA

Rated Load Amps

* Used to determine minimum disconnect per NEC (National Electrical Code).

NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at 0.3 FLA each.

41