Step 13 — Connect Air Pressure Tubing — Be- fore options such as the variable frequency drive (VFD) and/or modulating power exhaust can operate properly, the pneumatic tubing for pressure sensing must be installed. Use fire-retardant plenum tubing (field-supplied). All control devices use 1/4-in. tubing. Tubing must be run from the appropriate sensing loca- tion (in the duct or in the building space) to the control device location in the unit.

VARIABLE FREQUENCY DRIVE — The tubing for the duct pressure (DP) control option should sample supply duct pressure approximately 2/3 of the way out from the unit in the main trunk duct, at a location where a constant duct pressure is desired.

On these units, the duct pressure is sensed by a pressure transducer. The pressure transducer output is directed to the unit control module. On all sizes, the DP transducer is located in the unit auxiliary control box. See Fig. 44 and 45 for auxiliary control box location. See Fig. 46-48 for auxiliary control box details. Use a nominal 1/4-in. plastic tubing.

Refer to appropriate base unit Controls and Troubleshooting book for instructions on adjusting set points for duct pressure controls.

MODULATING POWER EXHAUST — The tubing for the building pressure (BP) control (achieved via the modulating power exhaust option) should sample building pressure in the

area near the entrance lobby (or other appropriate and sensitive location) so that location is controlled as closely to design pres- sures as possible.

These units use a pressure transducer for sensing building pressure. The BP transducer is located in the unit auxiliary con- trol box. See Fig. 44 and 45 for auxiliary control box location. See Fig. 46 and 47 for auxiliary control box details. Use a nom- inal 1/4-in. plastic tubing.

For instructions on adjusting BP control set points, refer to the Controls and Troubleshooting book.

RETURN FAN POWER EXHAUST — The tubing for the building pressure (BP) control (achieved via the return power exhaust option) should sample building pressure in the area near the entrance lobby (or other appropriate and sensitive lo- cation) so that location is controlled as closely to design pres- sures as possible.

The units use a pressure transducer for sensing building pressure. The BP transducer is located in the unit auxiliary con- trol box. See Fig. 45 for auxiliary control box location. See Fig. 48 for auxiliary control box details. Use a nominal 1/4 in. plastic tubing.

For instructions on adjusting BP control set points, refer to the Controls and Troubleshooting book.

AUXILIARY

CONTROL

BOX

Fig. 44 — Auxiliary Control Box Location (Sizes 030-050)

58

Page 58
Image 58
Carrier 48P2, P5030-100, P3, P4 installation instructions Auxiliary Control Box Location Sizes

P4, 48P2, P3, P5030-100 specifications

Carrier, a leader in the HVAC industry, offers a range of advanced air conditioning systems designed to provide optimal indoor climate control. Among their innovative products are the Carrier P4, P5030-100, P3, and 48P2 models, each delivering unique features tailored to diverse applications.

The Carrier P4 series is engineered for versatility and efficiency. This compact unit integrates advanced inverter technology, allowing for precise temperature control and reduced energy consumption. The P4 employs a variable speed compressor, which adjusts according to cooling needs, ensuring both comfort and energy savings. Additionally, it features a user-friendly interface with smart connectivity options, enabling remote access and management via smartphones.

Next in line, the Carrier P5030-100 model is designed with commercial applications in mind. It is equipped with a robust scroll compressor and advanced heat exchange technology that enhances its performance and efficiency. The P5030-100 operates quietly, making it ideal for office environments where noise reduction is a priority. Furthermore, its eco-friendly refrigerant aligns with today’s environmental standards, further making it a sustainable choice for businesses.

The Carrier P3 model excels in energy efficiency, boasting top SEER ratings while maintaining powerful cooling and heating capabilities. This model incorporates advanced refrigerant management, which minimizes environmental impact while ensuring optimal performance. Its compact design makes it an excellent choice for residential installations, providing homeowners with an unobtrusive yet effective climate control solution.

Finally, the Carrier 48P2 unit stands out with its robust design tailored for large-scale applications. It features a high-capacity scroll compressor and enhanced airflow capabilities, ensuring consistent and reliable performance across various conditions. The 48P2 comes equipped with a comprehensive control system that allows for integration with building management systems, facilitating easy monitoring and control of multiple units. This model is ideal for commercial buildings that demand high performance and energy efficiency.

Overall, Carrier's P4, P5030-100, P3, and 48P2 models represent the forefront of HVAC technology, combining efficiency, reliability, and advanced features to meet the varying demands of both residential and commercial environments. With a commitment to innovation and sustainability, Carrier continues to provide solutions that enhance indoor comfort while reducing environmental impact.