4
1
3
3
2
Fig. 8 — Gasket Location on Roof Curb
Step 8 — Connect Condensate Drain — There are a total of five drain connections required on each unit: one primary drain (on
PRIMARY DRAIN — The primary drain is a
With field-supplied fittings and pipe sections, plumb the pri- mary condensate drain to the 2-in. FPT connector on the base rail. Use a trap height of at least 4-in. for size 030-070 units and 7-in. for size 075-100 units. See Fig. 23 and 24. Install with a height dimension of at least 2-in. from the top of the exit pipe from the trap section to the bottom of the connector. Apply a bead of RTV or similar sealant around the pipe joint at the con- nector in the base rail.
SECONDARY DRAINS (Units Installed on Curb) — There are two secondary drain connections on each side of the unit. See Fig. 25. There are secondary drains on each side of the unit in the filter section and on each side of the unit in the supply fan section. There are labels marking each lo- cation on the unit base rail. See Fig.
Locate the four
At each secondary drain hole location, there is a
four
Using
Consult local plumbing codes for direction on joining multi- ple drain lines. Total size of any combined line does not need to exceed nominal
Fill the
SECONDARY DRAINS (Units Installed on Steel Beam or Slab) — There are two secondary drain connections required on each side of the unit. There are secondary drains on the bot- tom of the base rail on each side of the unit in the filter section and on each side of the unit in the supply fan section. There are labels marking each location on the unit base rail. See Fig. 12-
21.Drain holes will need to be drilled in these locations at the side of the base rail. The existing secondary drain holes in the bottom of the base rail must be sealed. Prior to final positioning of the unit, apply a bead of RTV or similar sealant around each secondary drain hole in the bottom of the unit base rail. See Fig. 27. Install the metal seal plates then position the unit into final location.
16