Carrier P4, P5030-100, P3, 48P2 installation instructions Voltage

Models: P4 48P2 P3 P5030-100

1 76
Download 76 pages 26.42 Kb
Page 39
Image 39
Manual background

Table 10 — Electrical Data, 48P2,P3,P4,P5030 Units (cont)

 

VOLTAGE

 

 

COMPRESSOR

 

CONDENSER

EVAPORATOR

POWER EXHAUST

POWER SUPPLY

VOLTAGE

RANGE

 

No. A1

 

No. B1

 

FAN MOTOR

FAN MOTOR

 

 

 

 

 

 

 

 

 

 

 

RLA

 

LRA

 

RLA

 

LRA

 

 

 

 

 

Hp

FLA

 

FUSE OR

3 PH, 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

Qty

 

Qty

 

Qty

FLA

Hp

FLA

Qty

MCA

HACR

 

 

(ea)

 

 

 

 

(ea)

 

(ea)

 

(ea)

 

(ea)

 

 

 

 

 

(ea)

 

BRKR*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

59.0

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

3.9

66.8

80

 

 

 

 

 

 

 

 

 

 

 

 

 

7 1/2

9.0

2

5

6.1

71.2

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

7.5

9.0

77.0

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

10

11.0

81.0

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

61.0

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

3.9

68.8

80

 

 

 

 

 

 

 

 

 

 

 

 

 

10

11.0

2

5

6.1

73.2

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

7.5

9.0

79.0

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

10

11.0

83.0

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67.0

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

3.9

74.8

90

 

 

 

 

 

 

 

 

 

 

 

 

 

15

17.0

2

5

6.1

79.2

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

7.5

9.0

85.0

100

575

518

632

1

19.9

 

109

1

19.9

 

109

2

2.6

 

 

2

10

11.0

89.0

100

 

 

(ea)

 

 

72.5

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

3.9

80.3

100

 

 

 

 

 

 

 

 

 

 

 

 

 

20

22.0

2

5

6.1

84.7

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

7.5

9.0

90.5

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

10

11.0

94.5

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

78.8

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

3.9

86.6

110

 

 

 

 

 

 

 

 

 

 

 

 

 

25

27.0

2

5

6.1

91.0

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

7.5

9.0

96.8

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

10

11.0

100.8

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85.0

110

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

3.9

92.8

110

 

 

 

 

 

 

 

 

 

 

 

 

 

30

32.0

2

5

6.1

97.2

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

7.5

9.0

103.0

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

10

11.0

107.0

125

 

 

LEGEND

FLA

Full Load Amps

HACR

Heating, Air Conditioning, and Refrigeration

Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

RLA

Rated Load Amps

* Used to determine minimum disconnect per NEC (National Electrical Code).

NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at 0.3 FLA each.

39