CPVS Model | 40 | 50 | 60 | 75 | |
|
|
|
|
|
|
Motor power | (hp) | 40 | 50 | 60 | 75 |
|
|
|
|
|
|
|
| Main Voltage 460 Volt / 3 / 60 Hz |
|
| |
|
|
|
|
|
|
Nominal current | (A) | 69 | 81 | 89 | 125 |
Power supply cable |
| AWG 4 | AWG 3 | AWG 1 | AWG 0 |
Fuse protection | (Type RK5) | 80 | 100 | 125 | 150 |
|
|
|
|
|
|
|
|
|
|
|
|
Connection of the electric plate to an external control box
•Install an RC filter on the KM1 coil.
•Install an RC filter on the KM2 coil.
•All connections between external parts and the compressor must be carried out using a shielded cable, which must be grounded at one of its ends.
WARNING: the operation connection cables between the different elements must never follow the same path as the existing power cords. A separate installation from the power cords must be carried out.
•Install an RC filter on all the relay coils of the external operation units.
Chicago Pneumatic Compressors | 01/2008 |
62 305 258 65 | Page 3 |