TABLE 9: Electrical Data - 3 Ø - 208/230-3-601

 

Heater2

Max. Static

 

 

Total Heat

 

 

 

KW Staging3

 

 

Models F*FP

& Min. CFM

 

 

 

 

 

 

 

 

 

 

 

KW

 

MBH

W1 Only

W2 Only

W1 + W2

Model

 

 

 

Static

Tap

208

 

240

208

240

208

240

208

240

208

240

024

2HK06501025B

0.5

Low

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

030

2HK06501025B

0.5

Low

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

2HK06501525B

0.5

High

11.3

 

15.0

38.6

51.2

3.8

5.0

7.5

10.0

11.3

15.0

 

 

036

2HK06501025B

0.5

Low

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

2HK06501525B

0.5

High

11.3

 

15.0

38.6

51.2

3.8

5.0

7.5

10.0

11.3

15.0

 

 

040

2HK06501025B

0.5

Low

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

2HK06501525B

0.5

High

11.3

 

15.0

38.6

51.2

3.8

5.0

7.5

10.0

11.3

15.0

 

 

042

2HK06501025B

0.5

Low

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

2HK06501525B

0.5

Low

11.3

 

15.0

38.6

51.2

3.8

5.0

7.5

10.0

11.3

15.0

 

 

045

2HK06501025B

0.5

Med

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

2HK06501525B

0.5

High

11.3

 

15.0

38.6

51.2

3.8

5.0

7.5

10.0

11.3

15.0

 

 

048

2HK06501025B

0.5

Med Low

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

2HK06501525B

0.5

Med Low

11.3

 

15.0

38.6

51.2

3.8

5.0

7.5

10.0

11.3

15.0

 

 

060

2HK06501025B

0.5

Med

7.5

 

10.0

25.6

34.1

3.8

5.0

7.5

5.0

7.5

10.0

2HK06501525B

0.5

Med

11.3

 

15.0

38.6

51.2

3.8

5.0

7.5

10.0

11.3

15.0

 

 

1.Heat amps shown at 240V represents maximum heater rating.

2.Heaters are 3 Phase.

3.If first stage heat or 66 is connected to W1, otherwise refer to this table.

TABLE 10: Electrical Data - (For Single Source Power Supply) - Copper Wire 3 Ø - 208/230-3-601

 

Heater2

 

 

Field Wiring

 

 

Models F*FP

Min. Circuit Ampacity

Max. O.C.P.3 Amps/Type

75°C Wire Size - AWG

Model

 

 

208V

240V

208V

240V

208V

240V

024

2HK06501025B

41.2

46.5

45

50

8

8

030

2HK06501025B

42.2

47.4

45

50

8

8

2HK06501525B

42.2

47.4

45

50

8

8

 

036

2HK06501025B

43.1

48.2

45

50

8

8

2HK06501525B

43.1

48.2

45

50

8

8

 

040

2HK06501025B

42.2

47.4

45

50

8

8

2HK06501525B

42.2

47.4

45

50

8

8

 

042

2HK06501025B

44.2

49.1

45

50

8

8

2HK06501525B

44.2

49.1

45

50

8

8

 

045

2HK06501025B

42.8

47.9

45

50

8

8

2HK06501525B

42.8

47.9

45

50

8

8

 

048

2HK06501025B

48.3

53.9

50

60

8

6

2HK06501525B

48.3

53.9

50

60

8

6

 

060

2HK06501025B

48.3

53.9

50

60

8

6

2HK06501525B

48.3

53.9

50

60

8

6

 

1.Heat amps shown at 240V represents maximum heater rating.

2.Heaters are 3 Phase.

3.O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.