Coleman F*FP Drain Connections, Maintenance, Coil Cleaning, Lubrication, Condensate Drains, 5005

Models: F*FP

1 16
Download 16 pages 28.56 Kb
Page 16
Image 16
DRAIN CONNECTIONS

DRAIN CONNECTIONS

All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection.

The drain pan connections are designed to ASTM Standard D 2466 Schedule 40. 3/4" PVC is preferred. Since the drains are not subject to any pressure it is not necessary to use Schedule 40 pipe for drain lines.

It is recommended that all drain connections be sealed with teflon tape or equivalent.

Threaded drain connection should be hand-tightened, plus no more than one turn.

Horizontal drain cutout in the center access panel should be removed by using a utility knife. DO NOT TRY TO KNOCK OUT.

Route the drain line so that it does not interfere with accessibility to the coil, air handling system or filter and will not be exposed to freezing temperatures. See Figures 2, 3 and 4.

NOTE: When the coil is installed in an attic or above a finished ceiling, an auxiliary drain pan should be provided under the coil as is specified by most local building codes.

Coils should be installed level or pitched slightly toward the drain end. Suggested pitch should not exceed 1/4 inch per foot of coil.

The coil is provided with a secondary drain that should be trapped and piped to a location that will give the occupant a visual warning that the primary drain is clogged. If the secondary drain is not used it must be capped.

MAINTENANCE

Filters must be cleaned or replaced when they become dirty. Inspect at least once per month. The frequency of cleaning depends upon the hours of operation and the local atmospheric conditions. Clean filters keep unit efficiency high.

COIL CLEANING

If the coil needs to be cleaned or replaced, it should be washed with Calgon CalClean (mix one part CalClean to ten parts water). Allow solu- tion to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact with painted sur- faces.

LUBRICATION

The bearings of the blower motor are permanently lubricated.

CONDENSATE DRAINS

During the cooling season check the condensate drain lines to be sure that condensate is flowing from the primary drain but not from the sec- ondary drain. If condensate ever flows from the secondary drain the unit should be promptly shut off and the condensate pan and drains cleaned to insure a free flowing primary drain.

 

 

TROUBLESHOOTING GUIDE

 

 

 

PROBLEM

 

POSSIBLE CAUSE

 

 

 

 

1.

No heat units do not have 6-pin connector installed.

 

2.

Limit open or not connected.

Blower Runs all of the time

3. Variable speed break-out tab broken out.

 

4.

Blower OFF delay (approx. 1 min).

 

5.

Thermostat fan switch in “ON” position.

 

 

Blown Fuse

1. Low voltage short to C or ground from R, Y, G, W, or O.

 

1.

4-pin connector loose.

No 24V

2. Loose wire from control to transformer (24V and 230V).

 

3.

Blown fuse on control board.

 

 

 

No 2nd stage heat

1.

Check 6-pin connector and connections to panel mount relays.

2.

Verify that both W1 & W2 are connected at the terminal strip.

 

 

 

 

 

1.

Check filter.

 

2.

Closed registers.

No Heat or Limited Heating

3. Restricted airflow (supply registers or return registers)

 

4.

Check blower motor operation.

 

5.

If the safety limit opens 4 times, the control will not permit the heating element to operate for 1 hour.

 

 

 

Subject to change without notice. Printed in U.S.A.

292043-UIM-B-0707

Copyright © by York International Corp. 2007. All rights reserved.

Supersedes: 292043-UIM-A-0507

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

Page 16
Image 16
Coleman F*FP Drain Connections, Maintenance, Coil Cleaning, Lubrication, Condensate Drains, Troubleshooting Guide, Unitary