TABLE 12: Airflow Data1 for 208 Volt - Heat Pump Models
| Blower Motor |
|
|
|
| 208 Volt |
|
|
|
| ||
Models |
|
|
| CFM @ External Static Pressure - IWC |
|
|
| |||||
Speed |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
| ||
|
| 0.10 | 0.20 | 0.30 | 0.40 | 0.50 | 0.60 | 0.70 | 0.80 | 0.90 | 1.00 | |
| High | 855 | 819 | 779 | 752 | 698 | 657 | 596 | 531 | 452 | 360 | |
F4FP024H06T2* | Med. | 760 | 733 | 706 | 670 | 634 | 589 | 535 | 472 | 395 | 310 | |
| Low | 585 | 567 | 545 | 518 | 486 | 457 | 405 | 344 | 257 | 142 | |
| High | 1143 | 1089 | 1035 | 977 | 914 | 851 | 776 | 692 | 581 | 451 | |
F4FP030H06T2* | Med. | 941 | 936 | 895 | 837 | 770 | 724 | 643 | 562 | 445 | 328 | |
| Low | 770 | 738 | 702 | 662 | 612 | 561 | 495 | 402 | 300 | 171 | |
| High | 1235 | 1179 | 1125 | 1058 | 1008 | 947 | 885 | 804 | 701 | 580 | |
F4FP036H06T2* | Med. | 1080 | 1035 | 990 | 936 | 887 | 840 | 791 | 716 | 640 | 528 | |
| Low | 954 | 914 | 873 | 833 | 774 | 728 | 666 | 595 | 515 | 408 | |
| High | 1143 | 1089 | 1035 | 977 | 914 | 851 | 776 | 692 | 581 | 451 | |
F4FP040H06T2* | Med. | 941 | 936 | 895 | 837 | 770 | 724 | 643 | 562 | 445 | 328 | |
| Low | 770 | 738 | 702 | 662 | 612 | 561 | 495 | 402 | 300 | 171 | |
| High | 1400 | 1418 | 1350 | 1278 | 1215 | 1145 | 1073 | 991 | 897 | 784 | |
F4FP042H06T2* | Med. | 1314 | 1266 | 1197 | 1135 | 1071 | 1012 | 947 | 864 | 758 | 625 | |
| Low | 1125 | 1080 | 1040 | 990 | 945 | 901 | 838 | 766 | 676 | 568 | |
| High | 1418 | 1382 | 1328 | 1251 | 1179 | 1120 | 1032 | 927 | 807 | 661 | |
F4FP045H06T2* | 1238 | 1184 | 1130 | 1067 | 999 | 936 | 850 | 763 | 659 | 545 | ||
1089 | 1044 | 999 | 945 | 882 | 829 | 760 | 663 | 576 | 480 | |||
| ||||||||||||
| Low | 932 | 891 | 846 | 801 | 743 | 693 | 628 | 554 | 472 | 389 | |
| High | 2209 | 2140 | 2093 | 2000 | 1939 | 1864 | 1746 | 1724 | 1655 | 1587 | |
| Med High | 1945 | 1906 | 1871 | 1819 | 1784 | 1741 | 1667 | 1640 | 1595 | 1550 | |
F5FP048H06T2* | Med | 1739 | 1690 | 1640 | 1602 | 1559 | 1516 | 1470 | 1431 | 1387 | 1343 | |
| Med Low | 1506 | 1464 | 1415 | 1369 | 1325 | 1283 | 1238 | 1193 | 1139 | 1100 | |
| Low | 1301 | 1248 | 1197 | 1151 | 1095 | 1054 | 1005 | 958 | 909 | 860 | |
| High | 2134 | 2124 | 2052 | 1979 | 1861 | 1756 | 1639 | 1597 | 1512 | 1427 | |
| Med High | 1916 | 1875 | 1838 | 1777 | 1744 | 1671 | 1594 | 1584 | 1537 | 1490 | |
F5FP060H06T2* | Med | 1716 | 1671 | 1613 | 1569 | 1523 | 1475 | 1429 | 1384 | 1337 | 1290 | |
| Med Low | 1494 | 1435 | 1390 | 1341 | 1284 | 1241 | 1194 | 1139 | 1087 | 1036 | |
| Low | 1276 | 1223 | 1168 | 1115 | 1068 | 1009 | 965 | 902 | 847 | 792 | |
| High | 2057 | 1976 | 1895 | 1814 | 1728 | 1661 | 1593 | 1517 | 1431 | 1337 | |
F4FV060H06T2* | Med. | 1913 | 1818 | 1719 | 1625 | 1535 | 1437 | 1342 | 1247 | 1152 | 1057 | |
| Low | 1490 | 1445 | 1395 | 1350 | 1305 | 1258 | 1194 | 1120 | 1038 | 946 | |
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: Air flow data shown above 0.50” W.C. external static pressure is for REFERENCE ONLY. Maximum allowable external static when electric heat is used is limited to 0.50” W.C. Maximum allowable external static pressure may also be limited by minimum CFM requirements for proper Heat Pump operation.
1. Includes Return Air Filter and Largest Electric Heater.
All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.
14 | Unitary Products Group |