•If the suction line is 3/4" diameter - position the bulb near the top of the copper tube as shown. If the tube is 7/8" diameter - position the bulb near the bottom of the tube. Refer to Figure 7.
•Wrap the clamp, bulb & line securely with insulation provided.
TAIL
END
UP
*
ROTATE BULB TO KEEP
TAIL AT BOTTOM
VERTICAL
RISER
FIGURE 7: Bulb Location
COIL UNDER PRESSURE.
Relieve pressure by removing plug from piping connection. Coil will have factory installed TXV. See outdoor unit documentation for cor- rect TXV to be used. Refer to unit nameplate for TXV identification for this unit.
NOTE: The coil should be open to the air for no more than 2 minutes to keep moisture and contaminates from entering the system. If the coil cannot be brazed into the refrigeration system in that time, the ends should be temporarily closed or plugged. For a short term delay, use masking tape over the ends of the copper tubing to close the tube to the air. For a longer term delay, use plugs or caps. There is no need to purge the coil if this procedure is followed.
REFRIGERANT LINE CONNECTION
See the outdoor unit installation instructions for the procedure to install field supplied tubing for systems with sweat fittings.
Stub adapters are available to adapt sweat connections to quick con- nections.
Connect lines as follows:
NOTE: Route the refrigerant lines to the coil in a manner that will not obstruct service access to the coil, air handling system or filter.
1. | Suction line connections are made outside the center access |
| panel. Center access panel is recessed to assure sufficient room |
| for brazing or it can be removed and slid over the suction line dur- |
| ing brazing. |
2. | Plan for TXV bulb placement. |
3. | Remove rubber plugs from refrigerant lines. |
4. | Braze the suction line. |
| been removed. |
only, install the
FAN CONNECTIONS | FAN RELAY | |||
TRANSFORMER |
| F |
|
|
CONNECTIONS | L | A | L |
|
2 | N | 1 |
| |
(HIGH VOLTAGE) |
|
| K2 T9A |
|
| L |
| L |
|
2 |
| 1 |
| |
|
|
|
|
CONNECTOR
L2 | 1 |
H 2 | K1 | T9A | |
L 3 |
|
| |
|
| (LIMIT, 2ND, 3RD | |
L 4 |
|
| |
|
|
| & 4TH HEAT RELAY |
1 STAGE |
|
| DRIVER) |
HEAT RELAY |
| & | LIM |
| HEAT | ||
|
| FAN | & |
|
| LIM | COM |
|
| PWR | TEST |
BREAK TAB FOR |
|
| |
VARIABLE SPEED MOTOR |
|
24 VOLT R | HEAT 2 | HEAT 4 |
|
| DRV HEAT 3 | DRV |
|
| DRV | ECM |
|
| 2 |
| |
| 4 | LTRIP |
|
| C |
| |
| V |
|
|
| A |
|
|
5 AMP | 5 | SPEED2 | 24 VOLT |
M | |||
CONTROL | A | COMMON | |
P | |||
VOLTAGE | M |
|
|
X |
|
| |
| A |
|
|
FUSE |
|
|
|
| R Y G W2 W1 O | C |
|
FIGURE 8: Control Board
Mark the unit nameplate with the appropriate heater selection on the space provided or NONE to indicate cooling only. To operate these units with electric heat, it is necessary to field install an electric heater kit (2HK). See Electric Heater Kit Accessory Installation instructions for proper installation procedure. Prior to installing electric heat, it is neces- sary to perform the following procedure:
1.Remove the
NOTE: This pin must not be used when electric heaters are installed.
2.Remove the four (4) screws from the duct cover and remove the duct cover from the air handler.
If unit is to be installed for right hand air flow, the circuit breakers in the heat kit will need to be removed and rotated 180°, so the OFF position will be down when the cabinet is positioned on the right side. This is an NEC requirement. Do One Breaker At A Time - to make sure wires are reconnected properly. Loosen terminal screws on the wires and gently pull the wires back from the breaker. Remove screws securing the breaker plate and rotate 180°, then secure the breaker plate and reconnect the wires to the breaker. Proper torque for terminal screws is 35 in/lbs.
REMOVE 3 SCREWS TO | HEAT KIT ASSEMBLY |
REMOVE THE CIRCUIT |
|
BREAKER BRACKET |
|
FROM HEAT KIT ASSEMBLY |
|
5. | Braze the liquid line. |
6. | Install supplied grommets on both the suction and liquid lines to |
| complete the air seal. |
7. | See previous section for TXV bulb. |
Lines should be sound isolated by using the appropriate hangers or strapping.
When field supplied lines are used be sure to insulate the suction line only.
ELECTRIC HEATERS & OPERATING CON- TROLS
JUMPER BAR
JUMPER BAR COVER
FIELD SUPPLY WIRING WILL BE ATTACHED TO THIS SIDE OF THE CIRCUIT BREAKER(S)
CIRCUIT BREAKER(S) - THERE MAY BE ONE, TWO OR THREE
HEAT KIT WIRING WILL BE ATTACHED TO THIS SIDE OF THE CIRCUIT BREAKER(S)
CIRCUIT BREAKER BRACKET
The low voltage transformer and fan / heater control, are standard on all models. See Figure 8. The air handlers are shipped
FIGURE 9: Electric Heaters in Horizontal Configuration - Right Hand Air Flow
6 | Unitary Products Group |