H o w i t Wo r k s : C o m p o n e n t L i s t i n g
Water system
•Motor/Pump assembly - The motor/pump assembly circulates chilled coolant through the process loop. The pump assembly is built with brass to maintain water quality.
Refrigeration system
•Compressor - Hermetic compressor takes
•
•Fan cycling switch - The fan cycling switch is adjustable when the chiller is in an environment cooler than 95°F {35°C}. See Appendix J entitled, Plumbing Schematic.
•
•Liquid receiver - Serves as a collection tank for
•Refrigerant sight glass - The refrigerant sight glass indicates refrigerant charge and moisture content. Refrigerant charge is determined by a clear liquid flow. Bubbles indicate low refrigerant. Moisture content is indicated by the color of the sight glass view port element. The element’s color is normally green. If the color of the element is dark brown or yellow, the system has been contaminated with moisture and the refrigerant circuit needs to be serviced by a qualified refrigerant service technician. See Maintenance section entitled, Checking the Refrigerant Charge and Quality.
•Expansion valve - The expansion valve meters flow of liquid refrigerant into the evaporator and creates a pressure drop in the refrigerant system that allows the liquid refrigerant to “boil off” inside the evaporator.