H o w i t Wo r k s : C o m p o n e n t L i s t i n g

Water system

Motor/Pump assembly - The motor/pump assembly circulates chilled coolant through the process loop. The pump assembly is built with brass to maintain water quality.

Refrigeration system

Compressor - Hermetic compressor takes low-pressure, low-temperature refrigerant gas and compresses the gas into high-pressure, high-temperature vapor.

Air-cooled condenser - The air-cooled condenser removes heat BTUs from the compressor refrigerant gas. The action causes the gas to “condense” into a liquid state still under high pressure. Air flow across the condenser is achieved by a motor driven fan.

Fan cycling switch - The fan cycling switch is adjustable when the chiller is in an environment cooler than 95°F {35°C}. See Appendix J entitled, Plumbing Schematic.

Filter-dryer- The filter-drier removes contaminants and moisture from the liquid refrigerant.

Liquid receiver - Serves as a collection tank for high-pressure liquid refrigerant to ensure total charge at all times.

Refrigerant sight glass - The refrigerant sight glass indicates refrigerant charge and moisture content. Refrigerant charge is determined by a clear liquid flow. Bubbles indicate low refrigerant. Moisture content is indicated by the color of the sight glass view port element. The element’s color is normally green. If the color of the element is dark brown or yellow, the system has been contaminated with moisture and the refrigerant circuit needs to be serviced by a qualified refrigerant service technician. See Maintenance section entitled, Checking the Refrigerant Charge and Quality.

Expansion valve - The expansion valve meters flow of liquid refrigerant into the evaporator and creates a pressure drop in the refrigerant system that allows the liquid refrigerant to “boil off” inside the evaporator.

2 - 6 l D e s c r i p t i o n

(continued)