C h i l l e r O p e r a t i o n S e q u e n c e
The EarthSmart ECM Series Chiller has a unique user interface that controls the process temperature and prevents refrigeration migration during compressor off times.
When the main power is connected:
1Depending on the state of the refrigeration system, the compressor may turn on momentarily upon connecting power. The compressor will stop when the refrigerant is pumped into the condenser and a low pressure condition exists in the evaporator.
When the power toggle switch is turned to the “On”or “I” position:
2Turning the toggle switch on immediately starts the process pump and illuminates the control. When flow is established and the unit is not in a low temperature alarm, the Liquid Line Solenoid valve (LLSV) will open. This allows the refrigerant to migrate to the evaporator and increase the pressure. When the low refrigerant pressure switch is satisfied the compressor will turn on and process coolant will begin cooling.
3When the process temperature is above setpoint the compressor will run and the
4The controller stays in this alarm condition (A2.lo) until the temperature is 2°F {1.1°C} above the
(continued)
4 - 6 l O p e r a t i o n