CAUTION: The compressor can start immediately when the High Pressure “Reset” button is pressed.

R e s e t t i n g t h e H i g h P r e s s u r e S w i t c h o f t h e C o m p r e s s o r

The high refrigeration safety pressure switch shuts off the compressor immediately when the high refrigeration pressure reaches 230 PSI {15.9 bar} without going through pump down during a low pressure cycle. If the high pressure switch trips, it must be manually reset by pressing the “Reset” button on the switch. The compressor can start immediately when this is reset so caution should be exercised.

To reset the high refrigeration safety switch:

NOTE: The High Pressure Safety switch may not reset

due to the chiller’s refrigerant state. Allow the refrigerant to cool before attempting to reset.

1Be sure the main power is disconnected and the chiller is locked out. Always disconnect/unplug and/or lockout the main power source before opening the unit for servicing.

2Remove the chiller’s right-side panel, as viewed from the control.

3Locate the high refrigeration safety switch within the top portion of the chiller’s cabinet.

Reset

Button

4Push the “Reset” button, until there is a “click”.

5Replace the chiller’s right-side panel, as viewed from the control.

6Reapply main power.

4 - 8 l O p e r a t i o n