S p e c i f i c a t i o n s : E a r t h S m a r t T M E C M S e r i e s C h i l l e r s

B

A

MODEL

ECM-0.5

ECM-0.75

Performance characteristics

 

 

Capacity* tons

0.41

0.70

Compressor Hp {kW}

0.5 {0.37}

0.75 {0.56}

Pump Hp {kW}

0.25 {0.19}

0.5 {0.37}

Chilled water flowgpm {lpm}

0.9 {3.4}

1.7 {6.4}

Chilled water pressurepsi {bar}

60 {4.1}

60 {4.1}

Reservoir capacity gal {liters}

10 {37.8}

10 {37.8}

Dimensions inches {mm}

 

 

A - Height

39.7 {1008}

39.7 {1008}

B - Width

18.7 {475}

18.7 {475}

C - Depth

24.2 {615}

24.2 {615}

Process connections inches {mm}

 

 

Process (to and from)

0.5

0.5

Weight lb {kg}§

 

 

Installed

223 {101}

233 {106}

Shipping

170 {77}

180 {82}

Voltages full load amps**

 

 

115V/1 phase/60Hz

14

NA

220V/1 phase/60Hz

NA

11

Refrigerant

 

 

 

R-134A

Refrigerant charge lb {kg}

 

 

 

1.3 {0.6}

1.3 {0.6}

 

 

 

SPECIFICATION NOTES:

C

*Ton capacity at 12,000 BTU/ton @ 50°F {10°C} leaving water temperature @ 115°F {46°C} condensing tempera- ture. Capacities may be ± 5% as reserved by the compressor manufacturer. Capacity multipliers are: 50°F {10°C} - 1.00; 40°F {4.4°C} - 0.80.

The ECM Series Chiller uses a hermetic reciprocating compressor.

Consult pump curve for exact characteristics relating to pump performances.

§Chiller installed weight includes a completely filled reservoir.

** No allowance for inrush current. Ground fault interruption to be supplied by the customer. Full load amps must be used to size supply conductors. Consult a Conair representative for 50 Hz operation.

Specifications can change at any time. Contact your Conair representative for the most current information.

2 - 8 l D e s c r i p t i o n

TPHS039-1208