NOTE: Models must be positioned so that the condenser air inlet is no warmer than 95°F {35°C} and the condenser air outlet is not blocked or restricted in any way.

NOTE: Locate models away from heat producing equip- ment. These items will affect ambient air conditions and the performance of the chiller.

P r e p a r i n g f o r I n s t a l l a t i o n

Plan the location for the chiller and prepare the area properly.

Position the chiller as close to the process machine as possible. Place the chiller in position near the process machine so that coolant lines can be connected from the process machine to the chiller and back.

Chiller

Process machine

Alternate locations

Make sure the area where the chiller is installed has:

A grounded power source.

Check the chiller’s serial tag for the correct amps, voltage, phase and cycle. All wiring should be completed by a qualified technician and comply with your region’s electrical codes.

Clearance for safe operation and maintenance.

Ensure there is 2 ft {0.6 m} of clearance at the air intake and 2 ft

{0.6 m} of clearance at the exhaust discharge for proper operation. Air flow is generated by the motor driven fan. Air flow is from the outside of the chiller, through the condenser and exhausted through the unit.

Exhaust air can not be ducted on motor driven fan models.

Position the locking casters to prevent the chiller from moving. For maintenance and servicing, be sure there is enough clearance to remove all access panels completely.

Available water source.

Ensure water make-up source is plumbed to the chiller’s installation location. High points in the plumbing require vent valves; low points require drain valves.

3 - 4 l I n s t a l l a t i o n