WARNING: Ice maker will not operate properly when water supply temperature is below 50_F. or above 100_F. Water supply flowing pressure must not exceed 50 PSI.

STARTING THE UNIT

After the ice cuber has been unpacked and leveled and all plumbing and electrical connections have been made, start the unit, and check for proper operation.

A cuber has three separate circuits: the water circuit, the refrigerant circuit and the electrical circuit.

1.Start checking the water circuit by making sure that there are not thread of flare joint leaks, either outside the unit or in the compressor section. Next check the water flow over the evaporator and make sure that all holes in the water distributor are open, (See Diagram 5) and that there is no undue splash or loss of water into the ice bin.

3/17/95

7