Cornelius 322 Compressor Contactor, Compressor & Starting Component Check-Out Procedure, Relay

Models: 322

1 32
Download 32 pages 61.15 Kb
Page 26
Image 26
COMPRESSOR CONTACTOR

Readings in the range listed below 100 Meg-Ohm would be an indicator that the system being tested may have a contamination problem. Where does the problem come from? As an example, the filter drier may become sat- urated and hold large percentages of moisture and the system function without a problem until such time as the product operating conditions change. Should the room temperature increase, or the condenser plug-up etc., the higher operating pressures and temperatures may cause the drier filter to release a portion of it’s held moisture. It is also imperative to avoid opening the sealed refrigeration system whenever possible and when it is done to be certain the true problem is correctly diagnosed and repaired. Remember, service gauge sets should only be installed after all external checks have been performed.

CAUTION: Megger checks should NEVER be performed on any compressor that is under a vacuum.

COMPRESSOR CONTACTOR

The contactor serves as the voltage supply switch for the compressor circuit. Voltage to the coil of the contactor is supplied by the circuit board.

Check Out:

The two (2)* line supply screws of the contactor should always have supply voltage present when voltage is on to the product.

The other two (2)* screws (load) should have line voltage when the contactor is energized. The contactor coil receives its supply voltage from the circuit board. Should the contactor fail to energize:

Check for supply voltage from circuit board, lead connections to contactor coil, and ohms value of coil.

* (3) if the product is 3 phase

COMPRESSOR & STARTING COMPONENT CHECK-OUT PROCEDURE

When compressors fail to start or run properly, it is normally the external electrical supply or the compressor start components that are defective -- the overload protector, start and/or run capacitor, relay, circuit board, safety controls, etc.

1.Check voltage at compressor terminals. NO voltage will require checking the electrical circuit working back from the compressor to determine where the voltage supply is interrupted and correct as required. The load voltage, while compressor is trying to start, should not be less than 90% of rated required voltage.

Line voltage and wire size effect the life expectancy of the electrical components, compressor, motor winding, solenoid coils, etc.

Poor line quality voltage will cause many erratic electrical problems. Remember every electrical product, ice ma- chine, dispenser, walk-in, reach-in, air conditioner, etc. required proper power supply to operate. Be certain when voltage checks are performed that you are measuring load voltage, not line voltage.

2.A defective capacitor or start relay may prevent the compressor from starting. Should the compressor at- tempt to start, but is unable to do so, or if the compressor hums or trips off on the over protector, check the following:

NOTE: For 50 HZ application on dual rated 50/60 HZ models, load voltage while compressor is start- ing must not be less than 90% of 50 HZ

rating.

Relay

Potential --

For the potential type, contacts are normally closed. The start contacts open by C.E.M.F. generated by the com- pressor at approximately 80% of the normal operating speed. As the contacts open, only the start capacitor is removed from the start circuit. Both the start and run winding and the run capacitor remain in the circuit. This relay may or may not be directional in mounting.

3/17/95

23

166240008

Page 26
Image 26
Cornelius 322 manual Compressor Contactor, Compressor & Starting Component Check-Out Procedure, Relay, rating, Potential