installation into an approved masonry or zero clearance fireplaces, the use of single or
|
|
|
|
|
|
|
|
| DEFINED MINIMUM DISTANCES | CLEARANCE |
|
| TO COMBUSTIBLES |
|
|
|
|
|
|
|
|
|
|
| A. UNIT TO SIDEWALL | 7” |
|
| B. UNIT TO SIDE TRIM | 7” |
|
| C. UNIT TOP TO TOP TRIM | 9.25” |
|
| D. UNIT TOP TO MANTLE | 9.25 |
|
| E. HEARTH FLOOR TO MANTLE | 32” |
|
| F. NONCOMBUSTIBLE FLOOR PROTECTION, front | 6” |
|
| G. NONCOMBUSTIBLE FLOOR PROTECTION, sides | 6” |
|
|
|
|
|
|
|
|
|
FIGURE 11 shows the Country Flame shroud system. Black trim is standard and gold trim is OPTIONAL and must be ordered separately. New home construction normally will not require a shroud kit for the Crossfire because the fireplace opening can be finished out to exact Crossfire dimensions. For
3SHROUD PANELS, (Top, Left Side, Right Side, each painted black)
3BLACK TRIM PIECES, (Top, Left Side, Right Side,
2TRIM CORNER BRACKETS with Screws
1ROLL OF FIBERGLASS INSULATION
3SHROUD PANELS, (Top, Left Side, Right Side, each painted black)
3BLACK TRIM PIECES, (Top, Left Side, Right Side,
2TRIM CORNER BRACKETS with Screws
2ROLLS OF FIBERGLASS INSULATION
SHROUD INSTALLATION INSTRUCTIONS1.Complete the Crossfire chimney and combustion air (if required) installation before installing the Crossfire shroud. The Crossfire insert should be sitting in the hearth ready for positioning in its final location but pulled forward as far as the chimney connection will allow. Open both the left and right access doors on the Crossfire. The installer can now begin installation of the shroud.
2.Remove the two
Version 2.0e | 25 |