Installation & Operation Manual
11 Maintenance Maintenance and annual startup
Table 11A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
| General: |
|
|
|
| |
| • Address reported problems, if any |
| ||||
| • Inspect interior; clean and vacuum if | |||||
| necessary; |
|
|
|
| |
| • Clean condensate trap and fill with fresh | |||||
| water |
|
|
|
| |
| • Check for | leaks (water, gas, | flue, | |||
| condensate) |
|
|
| ||
| • Verify flue and air lines in good condition | |||||
| and sealed tight |
|
|
| ||
| • Check system | water | pressure/system | |||
UP- | piping/expansion tank |
|
| |||
• Check control settings |
|
| ||||
|
|
| ||||
START | • Check the ignition and both flame sense | |||||
electrodes (sand off any deposits; clean | ||||||
| ||||||
ANNUAL | and reposition) |
|
|
| ||
• Check wiring and connections |
| |||||
|
| |||||
| • Perform | checkout | and | |||
| performance verification per Section 9. | |||||
| • Flame inspection (stable, uniform) |
| ||||
| • Check both flame signals (at least 10 | |||||
| microamps at high fire) |
| ||||
| • Clean the heat exchanger |
| ||||
| • Test low water | cutoff (reference | the | |||
| Crest Service Manual). |
|
| |||
| If combustion | or | performance | |||
| indicate need: |
|
|
|
•Clean heat exchanger
•Remove and clean burner using compressed air only
•Clean the blower wheels
Owner maintenance
(see the Crest User’s Information Manual for
instructions)
| • Check boiler area |
Daily | • Check pressure/temperature |
| gauge |
| • Check vent piping |
| • Check air piping |
Monthly | • Check air and vent termination |
| screens |
| • Check relief valve |
| • Check condensate drain system |
|
|
| • Test low water cutoff |
Every | • Reset button (low water |
cutoff) | |
6 months | • Check boiler piping (gas and |
| |
| water) for leaks |
| • Operate relief valve |
|
|
End | • Shut boiler down (unless boiler |
of season | used for domestic hot water) |
months |
|
53