Installation & Operation Manual
5 Hydronic piping
Near boiler piping components
1. | Boiler piping: |
| Boiler system piping should be sized per the pipe |
| requirements listed in Tables 5A and 5C. |
2. | Boiler circulating pump: |
| Field supplied. When using Primary/Secondary piping the |
| boiler circulating pump should be sized per Table 5A. |
3. | Hot Water Generator circulating pump: |
| Field supplied. When installed in a Primary/Secondary |
| arrangement, the Crest requires an additional pump for |
NOTICE | A system supply sensor (factory supplied) | |
MUST BE installed with Primary/Secondary | ||
| ||
| systems for proper boiler operation. |
10.Y-Strainer:
Field supplied. A
the Hot Water Generator Loop. The pump should |
be sized per Table 5A. Consult the indirect water |
heater operating guide to determine flow characteristics |
for the selected product used. The pump’s total flow and |
heat requirements are the sum of the boiler and the indirect |
water heater. |
4. Boiler isolation valves: |
Field supplied. Full port valves are required. Failure |
to use full port valves could result in a restricted flow |
rate through the boiler. |
CAUTION
NOTICE
The maximum allowable water flow rate through a single Crest boiler is 350 GPM. Exceeding this flow rate will result in damage to the heat exchanger and/or piping.
Reference Table 5B1 for the minimum recommended flow rate through a single Crest boiler at full fire to maintain a 80°F temperature rise. Reference Table 5B2 for the absolute minimum flow rate through a single Crest boiler.
5. | Check valves: |
|
|
|
| Field supplied. Check valves are required for | |||
| installation as shown in FIG.’s | |||
| install check valves could result in a reverse flow | |||
| condition during pump(s) off cycle. |
| ||
6. | Domestic indirect hot water isolation valves: | |||
| Field supplied. Full port valves are required. Failure to use | |||
| full port valves could result in a restricted flow rate through | |||
| the boiler. |
|
|
|
7. |
|
| ||
| Field supplied. | An | ||
| recommended when storing domestic hot water above | |||
| 115°F (46°C). |
|
|
|
8. | Pressure relief valve: |
|
| |
| Factory supplied. The pressure relief valve is sized to | |||
| ASME specifications. |
|
|
|
9. | System temperature sensor: |
| ||
| Lochinvar supplies | a | system | temperature sensor. |
| The sensor is to be installed in the heating loop | |||
| downstream from the boiler hot water piping and | |||
| heating loop junction. | The | sensor should be | |
| located far enough downstream to sense system diluted | |||
| water temperature. |
|
|
|
Table 5B1 Minimum Flow Rate with the Boiler at Full Fire
TEMPERATURE RISE APPLICATIONS
MODEL | FLOW RATE (GPM) |
|
|
FB(N,L)1500 | 35 |
|
|
FB(N,L)2000 | 46 |
|
|
FB(N,L)2500 | 58 |
|
|
FB(N,L)3000 | 70 |
|
|
FB(N,L)3500 | 81 |
|
|
[Based on 80°F Temperature Rise]
Table 5B2 Absolute Minimum Flow Rate
ABSOLUTE MINIMUM FLOW RATE
MODEL | FLOW RATE (GPM) |
|
|
FB(N,L)1500 | 25 |
|
|
FB(N,L)2000 | 25 |
|
|
FB(N,L)2500 | 25 |
|
|
FB(N,L)3000 | 25 |
|
|
FB(N,L)3500 | 45 |
|
|
26