Crestron CEN-CN Ethernet/Cresnet Interface
Operations Guide - DOC. 5721 Ethernet/Cresnet Interface: CEN-CN 9
5. Refer to figure below. From the Setup menu, verify that Auto Baud
Search is checked.
Verifying Auto Baud Search
6. Refer to figure below. While the Viewport is displayed, select Setup |
Communications (alternatively, depress Alt+D) to open the Port
Settings dialog box.
Accessing the Port Settings Dialog Box
7. Select the appropriate connection type. Verify that an available COM
port (COM 1 is shown on the next page) is selected. Set the baud rate to
38400, the parity to None, the data bits to Eight, and the stop bits to
One. Refer to the dialog box shown on the next page for the remaining
settings and click the OK button as shown to save the settings and
close the box.