Dell 350 Marking the Rack, inch 0.625 inch 1.75 inches 1 U 0.625 inch, Rack Installation Guide

Models: 100 350 110

1 32
Download 32 pages 131 b
Page 13
Image 13
Manual background

Marking the Rack

1.Determine where you want to place the bottom of the system.

CAUTION: If you are installing more than one system, install the first sys- tem in the lowest available position in the rack.

2.Place the 1-U template over the front of the two-posts of the rack in the desired location.

3.Position the bottom of the template in line with the desired bottom position of the system chassis.

4.Mark the upper and lower-mounting positions on the vertical rails as shown by the V-notches on the sides of the template.

Each 1-U (1.75-inch) vertical space has three holes, with center-to-center spacing between holes (beginning at the center of the top hole of a 1-U space) of 0.625, 0.625, and 0.5 inch (see Figure 1-5).

0.5 inch

0.625 inch

1.75 inches (1 U)

0.625 inch

0.5 inch

Figure 1-5. Two-Post Open-Frame Relay Rack 1-U Hole Spacing

support.dell.com

Rack Installation Guide

1-7

Page 13
Image 13
Dell 350, 110, 100 manual Marking the Rack, inch 0.625 inch 1.75 inches 1 U 0.625 inch, Rack Installation Guide