Connectors

 

NOTE: One card slot is dedicated for redundancy.

 

 

Video

 

 

 

Video type

Integrated Matrox G200 with iDRAC

Video memory

256 MB

Expanded Operating Temperature

NOTE: When operating in the expanded temperature range, system performance may be impacted.

NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.

< 10% of annual operating hours

5 °C to 40 °C at 5% to 85% RH with 26 °C dew point.

 

NOTE: Outside the standard operating temperature

 

(10 °C to 35 °C), the system can operate down to 5

 

°C or up to 40 °C for a maximum of 10% of its annual

 

operating hours.

 

For temperatures between 35 °C and 40 °C, de-rate

 

maximum allowable dry bulb temperature by 1 °C per 175

 

m above 950 m (1 °F per 319 ft).

< 1% of annual operating hours

–5 °C to 45 °C at 5% to 90% RH with 26 °C dew point.

 

NOTE: Outside the standard operating temperature

 

(10 °C to 35 °C), the system can operate down to –5

 

°C or up to 45 °C for a maximum of 1% of its annual

 

operating hours.

 

For temperatures between 40 °C and 45 °C, de-rate

 

maximum allowable dry bulb temperature by 1 °C per 125

 

m above 950 m (1 °F per 228 ft).

Expanded Operating Temperature Restrictions

• Do not perform a cold startup below 5 °C.

 

 

• The operating temperature specified is for a

 

maximum altitude of 3048 m (10,000 ft).

 

• PCIe SSD is not supported.

 

• GPU is not supported.

 

• LRDIMM not supported.

 

• PCIe cards are not supported on slots 1 and 2.

 

• A maximum of eight hard drives are supported.

 

• Redundant power supplies are required.

 

• Non Dell qualified peripheral cards and/or peripheral

 

cards greater than 25 W are not supported.