66 | System Specifications
www.dell.com | support.dell.com
EnvironmentalAC Power Supply Unit Requirements DC Power Entry Module Requirement
Parameter Specifications
Operating:
Temperature 32° to 104°F (0° to 40°C)
Maximum altitude No performance degradation to 10,000 feet (3,048 meters)
Relative humidity 5 to 85 percent, noncondensing
Non-operating:
Temperature -40° to 158°F (-40° to 70°C)
Maximum altitude 15,000 feet (4,572 meters)
Relative humidity 5 to 95 percent, noncondensing
Parameter Specifications
Nominal Input Voltage 120 - 240 VAC 50/60 Hz
Maximum AC Power Supply Input 16 A @ 100 VAC per module
12 A @ 200 VAC per module
Maximum Thermal Output (3,172 W)
Maximum Thermal Output (2,906 W)
10,822 BTU/hour at 100/120 VAC
9,914 BTU/hour at 200/240 VAC
Maximum AC Supply Input Current (based on 2500
W output for 100/120V and 200/240V lines.) 11.6 A @ 100 VAC
9.7 A @ 120 VAC
8.0 A @ 200 VAC
6.7 A @ 240 VAC
Maximum System Power Input 3.5 KVA @ 100/120 VAC
3.2 KVA @ 220/240 VAC
Maximum Power Consumption 3,422 W at 100/120 VAC
3,156 W at 200/240 VAC
Parameter Specifications
Nominal Input Voltage -44 to 60 VDC
Maximum Current Draw (per DC PEM) 100 A
Maximum Thermal Output (2,590 W) 8,838 BTU/hour
Maximum Power Consumption 2,840 W