PD-01 PROFIBUS-DP Module

Item

Name

Type

 

Description

Default

13

LossSPComTreat

UINT

This variable indicates that the PD-01 will

0x0000

 

 

 

take action when the SP communication

 

 

 

 

(SCANport communication) is lost, the value

 

 

 

 

can be assigned as follows:

 

 

 

 

00

– Stop data exchange and report fault;

 

 

 

 

01

– Continue data exchange and report

 

 

 

 

 

alarm;

 

 

 

 

02

– Ignore and continue data exchange.

 

If the address in Data Output 1 ~ Data Output 4 is continuous, then set d_state to 1, PD-01 will get starting address from Data Output 1. The next data will be got from the address next to the starting address, and the reading length is determined by dout_len. If the MODBUS address for reading is discontinuous, please set d_state to 0, PD-01 will also get starting address from Data Output 1, but the difference is the other data will be got from the address saved in Data Output 2, Data Output 3 and Data Output 4 in order.

Example, if

 

Data Output 1

= 0x2100;

Data Output 2

= 0x2101;

Data Output 3

= 0x2102;

Data Output 4

= 0x2103;

dout_len = 0x0003;

The MODBUS address in Data Output 1~Data Output 4 is continuous, so you can set the d_state to 1, then PD-01 will monitor the address starting from Data Output 1, and monitor 3 words from VFD series Drives one time. When the dout_len is 3, PD-01 will ignore the address in Data Output 4. If d_state is set to 0, PD-01 will read data from the address in Data Output 1, and read data from the address in Data Output 2, and so forth.