PD-01 PROFIBUS-DP Module

Code

Meaning

Corrective actives

03

Illegal data value

1. Check the parameter data (PWE2) in PKW

 

The data value received in the

area, and refer the user manual of VFD series

 

command message is not

Drives.

 

available for the drives.

2. Check the PLC program to confirm the data

 

 

that transmitted to PD-01 from master is valid.

 

 

3. Re-supply power to PD-01.

 

 

 

04

Slave device failure

1. Check all data in PKW.

 

The drive is unable to perform the

 

2. Re-supply power to PD-01.

 

requested action.

 

VFD series Drives will not respond message to PD-01 if it receives an invalid message from PD-01, but error code shown in the table below will be displayed on the digital keypad.

Code

Meaning

Corrective actives

05

Reserved

 

06

AC Drive is busy

 

07

Reserved

 

08

Reserved

1. Please refer to section 4.2 in this manual

09

Check sum is error

and check the setting of VFD series Drives.

10

Time out

2. If the error still exists, return it to factory.

11

Baud rate or protocol is invalid

 

12

Message is too short

 

13

Message is too long

 

14

Message contain invalid character

 

32DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

Page 35
Image 35
Delta PD-01 user manual Code Meaning Corrective actives