Delta Temperature Controller User Manual
Display |
|
| Explanations | |
PV |
| SV | Status of the temperature controller | |
|
|
| The control modes include: ON/OFF, MANUAL, PID and PID | |
|
|
| PROG. Default = PID. Select “MANUAL” here. | |
Back to |
|
| Press | to return to the main screen. |
top |
|
| ||
|
|
|
|
Parameters relevant to MANUAL control
Press in the main screen of DTB to enter the “regulation mode”.
Display |
| Explanations | |
PV |
| SV | Status of the temperature controller |
or |
|
| Set up heating or cooling control cycle. Default = heating, 20 |
|
|
| seconds per cycle. |
|
|
|
|
Press in the main screen of DTB to enter the “operation mode”.
Display |
| Explanations |
PV | SV | Status of the temperature controller |
|
| Run/stop |
Set up the position of decimal point.
1 = value with decimal point; 2 = value without decimal point
Manually adjust the output percentage. Assume the percentage value = 50 and the cycle = 20 seconds plus heating control, the system will conduct heating output for 10 seconds and stop for the other 10 seconds.
3.3 PID
Press for 3 seconds in the main screen to enter the “initial setting mode”. Press several
times until the parameter is displayed.
| Display | |
PV |
| SV |
Back to
top
Explanations
Status of the temperature controller
The control modes include: ON/OFF, MANUAL, PID and PID PROG. Default = PID.
Press to return to the main screen.
Parameters relevant to PID control
Press in the main screen of DTB to enter the “regulation mode”.
© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED | - 17 - |