Delta Electronics DTA4896R1 How to Return to Default Settings in DTB, DTCOM Software, Display

Models: DTA4896R1 DTC1000R

1 25
Download 25 pages 25.55 Kb
Page 7
Image 7
1.3 How to Return to Default Settings in DTB

Manual background Delta Temperature Controller User Manual

DTCOM Software

Explanations

 

Clear the user’s settings.

 

Function address = 4724; Write data = 1234

 

(Please DO NOT modify this value; otherwise

 

system confusion may occur.)

 

 

 

After the above procedures are completed, DTA

 

will display the information on the left hand side,

 

representing that DTA has return to default

 

settings successfully.

Switch off DTA and re-power it.

 

 

 

 

Return to default value. The default sensor is

 

PT100, which will be displayed when DTA is not

 

connected to a sensor or thermocouple.

The model adopted in this example is: DTA4896R1 with firmware V3.50.

1.3 How to Return to Default Settings in DTB

 

Display

PV

 

SV

Manual backgroundManual background

Explanations

Status of the temperature controller

Temporary display when DTB is switched on: Manual background =

firmware V1.50; Manual background = relay output for OUT1/OUT2 Example displayed value

Press Manual background for 3 times Key-locked function

Select Lock 1

Press “up” and “down” key together for 1 second.

© DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

- 7 -

2007-09-17

Page 7
Image 7
Delta Electronics DTA4896R1, DTC1000R How to Return to Default Settings in DTB, DTCOM Software, Explanations, Display