Delta Electronics VFD-XXXM Parameter, Explanation, Settings, Factory, Customer, English-13

Models: VFD-XXXM

1 22
Download 22 pages 36.93 Kb
Page 13
Image 13
English-13

 

Parameter

Explanation

Settings

Factory

Customer

 

 

Setting

 

 

Pr.59

Electronic Thermal

30 to 300 sec

60

 

 

 

Motor Overload

 

 

 

 

 

 

 

 

 

 

 

00: Over-Torque Detection Disable

 

 

 

 

 

 

01: Enabled during constant speed

 

 

 

 

 

 

operation until the allowable time for

 

 

 

 

 

 

detection (Pr.62) elapses.

 

 

 

 

 

Over-Torque Detection

02: Enabled during constant speed

 

 

 

 

Pr.60

operation and halted after detection.

00

 

 

 

Mode

 

 

 

 

03: Enabled during acceleration until the

 

 

 

 

 

 

 

 

 

 

 

 

allowable time for detection (Pr.62)

 

 

 

 

 

 

elapses.

 

 

 

 

 

 

04: Enabled during acceleration and

 

 

 

 

 

 

halted after detection.

 

 

 

 

Pr.61

Over-Torque Detection

30 to 200 %

150

 

 

 

Level

 

 

 

 

 

 

 

 

 

Pr.62

Over-Torque Detection

0.0 to 10.0 seconds

0.1

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

00: Decelerate to 0 Hz

 

 

 

 

Pr.63

Loss of ACI (4-20mA)

01: Stop immediately and display "EF"

00

 

 

 

02: Continue operation by last frequency

 

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

00: Display AC drive output Frequency

 

 

 

 

 

 

(Hz)

 

 

 

 

 

 

01: Display User-defined output

 

 

 

 

 

 

Frequency (H*Pr.65)

 

 

 

 

 

 

02: Output Voltage (E)

 

 

 

 

 

 

03: DC Bus Voltage (u_)

 

 

 

 

 

 

04: PV (i)

 

 

 

 

Pr.64

User Defined Function

05: Display the value of internal counter

06

 

 

 

for Display

(c)

 

 

 

 

 

 

 

 

 

 

06: Display the setting frequency (F or

 

 

 

 

 

 

o=%)

 

 

 

 

 

 

07: Display the parameter setting (Pr.00)

 

 

 

 

 

 

08: Reserved

 

 

 

 

 

 

09: Output Current (A)

 

 

 

 

 

 

10: Display program operation (0.xxx),

 

 

 

 

 

 

Fwd, or Rev

 

 

 

 

Pr.65

Coefficient K

0.01 to 160.0

1.00

 

 

 

 

 

 

 

 

 

 

Pr.66

Communication

0.00 to 400.0 Hz

0.00

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

Pr.67

Skip Frequency 1

0.00 to 400.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

Pr.68

Skip Frequency 2

0.00 to 400.0 Hz

0.00

 

 

 

Pr.69

Skip Frequency 3

0.00 to 400.0 Hz

0.00

 

 

 

 

 

 

 

 

 

 

Pr.70

Skip Frequency Band

0.00 to 20.00 Hz

0.00

 

 

 

 

PWM Carrier

01 to 15

15

 

 

 

Pr.71

The factory setting of VFD075M43A is 10.

 

 

 

Frequency

 

 

 

 

 

575V series: 01 to 10

6

 

 

 

 

 

 

 

 

Pr.72

Auto Restart Attempts

00 to 10

00

 

 

 

after Fault

 

 

 

 

 

 

 

 

English-13