Delta Electronics VFD-XXXM Summary Of Parameter Settings, Explanation, Factory, Customer

Models: VFD-XXXM

1 22
Download 22 pages 36.93 Kb
Page 9
Image 9

SUMMARY OF PARAMETER SETTINGS

: The parameter can be set during operation

 

Parameter

Explanation

Settings

Factory

Customer

 

 

Setting

 

 

 

 

00: Master frequency determined by

 

 

 

 

 

 

digital keypad (LC-M02E)

 

 

 

 

 

 

01: Master frequency determined by 0 to

 

 

 

 

 

 

+10 V input on AVI terminal with

 

 

 

 

 

Source of Frequency

jumpers

 

 

 

 

Pr.00

02: Master frequency determined by 4 to

00

 

 

 

Command

20mA input on ACI terminal with

 

 

 

 

 

 

 

 

 

 

jumpers

 

 

 

 

 

 

03: Master frequency determined by RS-

 

 

 

 

 

 

485 Communication port

 

 

 

 

 

 

04: Master frequency determined by

 

 

 

 

 

 

potentiometer on digital keypad

 

 

 

 

 

 

00: Operation determined by digital

 

 

 

 

 

 

keypad

 

 

 

 

 

 

01: Operation determined by external

 

 

 

 

 

 

control terminals, keypad STOP is

 

 

 

 

 

 

effective

 

 

 

 

 

 

02: Operation determined by external

 

 

 

 

Pr.01

Source of Operation

control terminals, keypad STOP is

00

 

 

 

command

ineffective

 

 

 

 

 

 

 

 

 

 

03: Operation determined by RS-485

 

 

 

 

 

 

communication port, keypad STOP is

 

 

 

 

 

 

effective

 

 

 

 

 

 

04: Operation determined by RS-485

 

 

 

 

 

 

communication port, keypad STOP is

 

 

 

 

 

 

ineffective

 

 

 

 

Pr.02

Stop Method

00: Ramp stop

00

 

 

 

01: Coast Stop

 

 

 

 

 

 

 

 

 

Pr.03

Maximum Output

50.00 to 400.0 Hz

60.00

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

Maximum Voltage

 

 

 

 

 

Pr.04

Frequency (Base

10.00 to 400.0Hz

60.00

 

 

 

 

Frequency)

 

 

 

 

 

Pr.05

Maximum Output

115V/230V: 0.1 to 255.0V

220.0

 

 

 

460V: 0.1 to 510.0V

440.0

 

 

 

Voltage (Vmax)

 

 

 

 

575V: 0.1 to 637.0V

575.0

 

 

 

 

 

 

 

 

Pr.06

Mid-point Frequency

0.10 to 400.0Hz

1.50

 

 

 

 

 

115V/230V: 0.1 to 255.0V

10.0

 

 

 

Pr.07

Mid-point Voltage

460V: 0.1 to 510.0V

20.0

 

 

 

 

 

575V: 0.1 to 637.0V

26.1

 

 

 

Pr.08

Minimum Output Freq

0.10 to 20.00Hz

1.50

 

 

 

Pr.09

Minimum Output

115V/230V: 0.1 to 255.0V

10.0

 

 

 

460V: 0.1 to 510.0V

20.0

 

 

 

Voltage

 

 

 

 

575V: 0.1 to 637.0V

26.1

 

 

 

 

 

 

 

 

Pr.10

Acceleration Time 1

0.1 to 600.0 sec or 0.01 to 600.0 sec

10.0

 

 

 

Pr.11

Deceleration Time 1

0.1 to 600.0 sec or 0.01 to 600.0 sec

10.0

 

 

 

Pr.12

Acceleration Time 2

0.1 to 600.0 sec or 0.01 to 600.0 sec

10.0

 

 

 

Pr.13

Deceleration Time 2

0.1 to 600.0 sec or 0.01 to 600.0 sec

10.0

 

 

 

Pr.14

Accel S-curve

00 to 07

00

 

 

 

Pr.15

Jog Accel/Decel Time

0.1 to 600.0 sec or 0.01 to 600.0 sec

1.0

 

 

English-9

Page 9
Image 9
Delta Electronics VFD-XXXM Summary Of Parameter Settings, The parameter can be set during operation, Explanation, Factory