Delta Electronics VFD-XXXM Parameter, Explanation, Settings, Factory, Customer, English-17

Models: VFD-XXXM

1 22
Download 22 pages 36.93 Kb
Page 17
Image 17

 

Parameter

Explanation

Settings

Factory

Customer

 

 

Setting

 

 

Pr.119

Differential Time (D)

0.00 to 1.00 sec

0.00

 

 

 

 

 

 

 

 

 

 

Pr.120

Integration’s Upper

00 to 100 %

100 %

 

 

 

Bound Frequency

 

 

 

 

 

 

 

 

 

Pr.121

One-Time Delay

0.0 to 2.5 sec

0.0

 

 

 

 

 

 

 

 

 

 

Pr.122

PID Frequency Output

00 to 110 %

100

 

 

 

Command Limit

 

 

 

 

 

 

 

 

 

Pr.123

Feedback Signal

0.0: Disable

60.0

 

 

 

Detection Time

0.1 to 3600 sec

 

 

 

 

 

 

 

 

Pr.124

Feedback Signal Fault

00: Warning and RAMP to stop

00

 

 

 

Treatment

01: Warning and keep operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.125

Source of PID Set Point

0.00 to 400.0Hz

0.00

 

 

 

Pr.126

PID Offset Level

1.0 to 50.0 %

10.0

 

 

 

Pr.127

Detection Time of PID

0.1 to 300.0 sec

5.0

 

 

 

Offset

 

 

 

 

 

 

 

 

 

Pr.128

Minimum Reference

0.0 to 10.0 V

0.0

 

 

 

Value

 

 

 

 

 

 

 

 

 

Pr.129

Maximum Reference

0.0 to 10.0 V

10.0

 

 

 

Value

 

 

 

 

 

 

 

 

 

Pr.130

Invert Reference Signal

00: Not inverted

00

 

 

 

AVI (0-10V)

01: Inverted

 

 

 

 

 

 

 

 

Pr.131

Minimum Reference

0.0 to 20.0mA

4.0

 

 

 

Value (4-20mA)

 

 

 

 

 

 

 

 

 

Pr.132

Maximum Reference

0.0 to 20.0mA

20.0

 

 

 

Value (4-20mA)

 

 

 

 

 

 

 

 

 

Pr.133

Invert Reference Signal

00: Not inverted

00

 

 

 

(4-20mA)

01: Inverted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.134

Analog Input Delay

00 to 9999 (per 2ms)

50

 

 

 

Filter for Set Point

 

 

 

 

 

 

 

 

 

 

Analog Input Delay

 

 

 

 

 

Pr.135

Filter for Feedback

00 to 9999 (per 2ms)

5

 

 

 

 

Signal

 

 

 

 

 

Pr.136

Sleep Period

0.0 to 6550.0 sec

0.0

 

 

 

Pr.137

Sleep Frequency

0.00 to 400.0 Hz

0.00

 

 

 

Pr.138

Wake Up Frequency

0.00 to 400.0 Hz

0.00

 

 

 

Pr.139

Treatment for Counter

00: Continue operation

00

 

 

 

Attained

01: Stop Immediately and display E.F.

 

 

 

 

 

 

 

 

Pr.140

External Up/Down

00: Fixed Mode (keypad)

 

 

 

 

01: By Accel or Decel Time

00

 

 

 

Selection

 

 

 

 

02: Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.141

Save Frequency Set

00: Not Save

01

 

 

 

Point

01: Save

 

 

 

 

 

 

 

English-17