Delta Electronics VFD-XXXM Parameter, Explanation, Settings, Factory, Customer, English-15

Models: VFD-XXXM

1 22
Download 22 pages 36.93 Kb
Page 15
Image 15
English-15

 

Parameter

Explanation

Settings

Factory

Customer

 

 

Setting

 

 

Pr.84

Time Duration of 4th

00 to 9999 sec

00

 

 

 

Step Speed

 

 

 

 

 

 

 

 

 

Pr.85

Time Duration of 5th

00 to 9999 sec

00

 

 

 

Step Speed

 

 

 

 

 

 

 

 

 

Pr.86

Time Duration of 6th

00 to 9999 sec

00

 

 

 

Step Speed

 

 

 

 

 

 

 

 

 

Pr.87

Time Duration of 7th

00 to 9999 sec

00

 

 

 

Step Speed

 

 

 

 

 

 

 

 

 

Pr.88

Communication

01 to 254

01

 

 

 

Address

 

 

 

 

 

 

 

 

 

 

 

00: 4800 bps

 

 

 

 

Pr.89

Transmission Speed

01: 9600 bps

01

 

 

 

02: 19200 bps

 

 

 

 

 

 

 

 

 

 

 

03: 38400 bps

 

 

 

 

 

 

00: Warn and Continue Operating

 

 

 

 

Pr.90

Transmission Fault

01: Warn and RAMP to Stop

03

 

 

 

Treatment

02: Warn and COAST to Stop

 

 

 

 

 

 

 

 

 

 

03: Keep Operation without Warning

 

 

 

 

 

 

 

 

 

 

 

Pr.91

Time Out Detection

0.0: Disable

0.0

 

 

 

0.1 to 120.0 sec

 

 

 

 

 

 

 

 

 

 

 

00: MODBUS ASCII mode, <7,N,2>

 

 

 

 

 

 

01: MODBUS ASCII mode, <7,E,1>

 

 

 

 

Pr.92

Communication

02: MODBUS ASCII mode, <7,O,1>

00

 

 

 

Protocol

03: MODBUS RTU mode, <8,N,2>

 

 

 

 

 

 

 

 

 

 

04: MODBUS RTU mode, <8,E,1>

 

 

 

 

 

 

05: MODBUS RTU mode, <8,O,1>

 

 

 

 

 

 

 

 

 

 

 

Pr.93

Accel 1 to Accel 2

0.01 to 400.0

0.00

 

 

 

Frequency Transition

0.00: Disable

 

 

 

 

 

 

 

 

Pr.94

Decel 1 to Decel 2

0.01 to 400.0

0.00

 

 

 

Frequency Transition

0.00: Disable

 

 

 

 

 

 

 

 

Pr.95

Auto Energy Saving

00: Disable auto energy saving

00

 

 

 

01: Enable auto energy saving

 

 

 

 

 

 

 

 

 

Pr.96

Counter Countdown

00 to 9999

00

 

 

 

Complete

 

 

 

 

 

 

 

 

 

Pr.97

Preset counter

00 to 9999

00

 

 

 

countdown

 

 

 

 

 

 

 

 

 

Pr.98

Total Time Count from

00 to 65535 days

Read

 

 

 

Power On (Days)

Only

 

 

 

 

 

 

 

 

Pr.99

Total Time Count from

00 to 1440 minutes

Read

 

 

 

Power On (Minutes)

Only

 

 

 

 

 

 

 

 

Pr.100

Software Version

 

##

 

 

 

 

 

00: Linear Accel/Decel

 

 

 

 

 

 

01: Auto Accel, Linear Decel

 

 

 

 

Pr.101

Auto Adjustable

02: Linear Accel, Auto Decel

00

 

 

 

Accel/Decel

03: Auto Accel/Decel

 

 

 

 

 

 

 

 

 

 

04: Linear Accel/Decel Stall Prevention

 

 

 

 

 

 

during Deceleration

 

 

 

English-15