Installation
Continued
NOTICE: If your installation does not meet the minimum clear- ances shown, you must do one of the following:
•operate the logs only with the flue damper open
•raise the mantel to an accept- able height
•remove the mantel.
|
| 12" |
|
| Mantel Shelf |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| Underside | |||
|
| 10" |
|
|
|
|
|
|
| of Mantel | ||
|
| 8" |
|
|
|
|
|
|
| Shelf | ||
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 6" |
|
|
|
|
| All minimum | ||||
|
|
|
|
|
|
| ||||||
|
| 2 1/2" |
|
|
|
|
| |||||
|
|
|
|
|
|
|
| distances are | ||||
Minimum |
|
|
|
|
|
|
| in inches | ||||
|
|
|
|
|
|
|
|
|
|
|
| |
Noncombustible |
|
|
|
|
|
|
|
|
|
| Log Set | |
Material |
|
|
|
|
|
|
|
|
|
|
| |
| 8" |
| 12" | 15" | 18" | 20" |
|
| All | |||
|
|
| Min. |
|
|
|
|
|
|
| Models | |
|
|
|
|
|
|
|
|
|
| Top of | ||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| Fireplace | ||
|
| Hood | Distances to |
|
|
| Opening |
(GA6050, | Underside of | |
GA6052) | ||
Mantel | ||
|
Figure 7 - Minimum Mantel Clearances
When Using Hood
Floor Clearances
A.If installing appliance on the floor level, you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B.If combustible materials are less than 14" to the fireplace, you must install appliance at least 5" above the combustible flooring (see Figure 9).
Combustible
14" Material
Min.
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Hearth
Combustible Material
5"
Min.
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION
Note: When used as a vented heater, appliance must be installed only in a
If you choose to use your heater as a manually- controlled model (no remote control installed), you may use this heater as a vented product. There are three reasons for operating your heater in the vented mode.
1.The fireplace does not meet the clearance to combustibles requirements for
2.State or local codes do not permit
3.You prefer vented operation.
If reasons number 1 or 2 above apply to you, you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page 34). This will insure vented operation (see Figure 10, page 12). The damper clamp will keep damper open. Installation instruc- tions are included with clamp accessory.
See chart below for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.
Chimney | Minimum Permanent |
Height | Flue Opening |
|
|
6' to 15' | 39 sq. inches |
15' to 30' | 29 sq. inches |
Area of Various Standard Round Flues
Diameter (inches) | Area (sq. inches) |
|
|
5 | 0 |
6 | 9 |
7 | 39 |
8 | 51 |
www.desatech.com | 11 |