INSTALLATION
Continued
INSTALLATION CLEARANCES
Minimum clearances to combustible construction are:
• Top, Back and Sides of Recessed |
|
|
|
|
| ||||
| Cabinet | . | 0" Min. | • | Floor | . . | . | 0" Min. | |
• Drywall to Sides of Front Face . | . | 0" Min. | • | Front . . . . . . . . . . . .36" Min. | |||||
• | Framing at Nailing Flanges. . . |
| .0" Min. | • | Perpendicular Side Wall . . | . | . | 10" Min. | |
• | Ceiling to Opening | .36" Min. |
|
|
|
|
| ||
Mantel Clearances |
|
|
|
|
|
|
|
| |
For mantel clearances see Figures 3 and 4. |
|
|
|
|
| ||||
|
|
|
|
|
| Facing Material May |
|
|
|
|
|
|
|
|
| Be Noncombustible |
|
|
|
|
|
|
|
|
| Wall Treatments or |
|
|
|
|
|
|
| 12" Ref. |
| Combustible Wood |
|
|
|
|
|
|
| 10 1/2" |
| Combustible Wood |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| 4 1/2" |
| Mantels and Trims |
|
|
|
|
|
|
| 1 1/2" | May Extend Above |
|
|
| |
| 30° |
|
|
|
| Profile Shown when |
|
|
|
|
|
|
|
|
| Maintained within |
|
|
|
|
|
|
|
|
| 30° Parameter |
|
|
|
|
|
|
|
|
| Shown |
|
|
|
| 16 5/8" | 1 3/4" |
|
|
| Framed |
|
|
|
|
|
|
|
| Material |
|
|
| |
| Ref. |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
133/4"
Top of Cabinet
10 1/2" Min. | 9 5/8" Ref. |
Note: All Mantel Clearances are Measured from Top of Fireplace Opening
Figure 3 - Mantel Clearances
Top View of Fireplace
Edge of Firebox Opening
3"
| Safe Zone | |
30° | 5" | |
1 3/4" Max. | ||
|
Minimum 10" from
Perpendicular Side Wall
Combustible
MaterialMust
Not Overlap
Front Face
Figure 4 - Mantel Side Clearances
www.desatech.com111076-01F