VENTING INSTALLATION INSTRUCTIONS Installation Planning (Cont.)

VENTING INSTALLATION

INSTRUCTIONS

Continued

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives

for venting with horizontal termination. Each figure includes a chart

with critical minimum and maximum dimensions which MUST be

CORNER INSTALLATION

Recommended Applications:

Corner ground floor installation

Ground floor installation where pipe vents horizontally through wall (over 12" horizontal pipe)

Basement installation where one foot clearance from ground to termination is possible

met. IMPORTANT: Remember that a horizontal run of venting must

have a 1/4" rise for every 12" of run toward the termination.

WARNING: Never run vent downward as this may

cause excessive temperatures which could cause a

fire. Operation of improperly installed and maintained

venting system could result in serious injury, property

damage or loss of life.

45° Elbow

Horizontal High

Wind Square

Termination

Adjustable

Pipe 12" Max.

Not to Exceed

(H) Limits

Square Termination

Wall

Firestop

90° Elbow

As Required for (V)

See Chart for Pipe

Section Required

45° Elbow

Wall Firestop

 

 

 

Square Termination

Vertical (V)

Horizontal (H)

29

3

/4"

17" max.

 

 

Vertical (V)

Required

Vertical (V)

Vertical Pipe

Horizontal (H)

*43 3/4" min.

None

30" max.

53 3/4" min.

1 ft.

48" max.

65 3/4" min.

2 ft.

60" max.

77 3/4" min.

3 ft.

84" max.

89 3/4" min.

4 ft.

20' max.

* Ground Floor Corner Venting

45° Elbow

Wall

Firestop

Exterior Portion of

Wall Firestop (Round

Termination Only)

Horizontal

Round

Termination

GROUND FLOOR INSTALLATION

Recommended Applications:

Installation using cabinet surrounds

Through the wall using round or

 

square termination

 

(up to 12" horizontal pipe)

NOT FOR CORNER

Not to Exceed (H) Limits

90° Elbow

Wall

Firestop

45° Elbow

Square Termination

12" Minimum

INSTALLATION

Figure 15 - Horizontal Termination Configuration for Corner Installation Using One 90° Elbow

Figure 14 - Horizontal Termination Configuration for Square or Round Termination

www.desatech.com

116647-01A

Page 10
Image 10
Desa (V)T32EN-A Series, (V)T32EP-A Series Venting Installation, Instructions, Horizontal Termination Configurations, 17 max