VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

11

VENTING INSTALLATION

INSTRUCTIONS

Continued

SNORKEL TERMINATION INSTALLATION

Recommended Applications:

Installations requiring a vertical rise on building exterior

Any installation using snorkel termination to achieve one foot above ground

Snorkel terminations are available for installations requiring a vertical rise on the exterior of the building. If installing snorkel termina-

tion below grade, you must provide proper drainage to prevent water from entering snorkel termination (see Figure 16). Do not back fill

around snorkel termination.

 

 

Snorkel

 

Snorkel

 

Termination

 

 

 

Snorkel

Termination

 

 

 

 

 

Termination

 

Wall

 

 

 

 

 

90° Elbow

Firestop

12"

 

12"

 

Minimum

 

 

 

 

Minimum

 

 

 

45°

 

 

12"

Elbow

 

 

 

 

 

Minimum

Adequate

 

 

 

 

 

 

Drainage

 

 

Figure 16 - Snorkel Termination Configurations for Below Ground Installation

HORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWS

 

The following configurations show the minimum vertical rise requirements for a horizontal system using two 90° elbows.

Venting with Two 90° Elbows

 

 

 

 

 

 

Horizontal (H

) +

 

Vertical (V)

Horizontal (H

)

1

 

)

 

Horizontal (H

 

 

1

 

 

2

 

 

5' min.

2' max.

 

6' max.

 

 

 

6' min.

4' max.

 

12' max.

 

 

 

7' min.

6' max.

 

18' max.

 

 

 

8' min.

8' max.

 

20' max.

 

45°

Elbow

20' max.

8' max.

 

20' max.

 

 

 

 

 

Figure 17 - Horizontal Termination Configuration for Venting Using Two 90° Elbows

116647-01A

www.desatech.com

Page 11
Image 11
Desa (V)T32EN-A Series, (V)T32EP-A Series Venting with Two 90 Elbows, Horizontal H Vertical Min Max 12 max 18 max 20 max