Desa VTP22R, VTN25R installation manual Continued, Ventilation Air From Inside Building

Models: VTP22R VTN25R

1 48
Download 48 pages 27.8 Kb
Page 6
Image 6
Example:

AIR FOR COMBUSTION

AND VENTILATION

Continued

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr (kw) the space can support.

__________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr (kw) of all fuel burning appli- ances in the space.

Vent-free heater

________ Btu/Hr (kw)

Gas water heater*

________ Btu/Hr (kw)

Gas furnace

________ Btu/Hr (kw)

Vented gas heater

________ Btu/Hr (kw)

Gas fireplace logs

________ Btu/Hr (kw)

Other gas appliances* +________ Btu/Hr (kw)

Total

=________ Btu/Hr (kw)

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

40,000 (11.7)

 

Gas water heater

Btu/Hr (kw)

Vent-free heater

+ 22,000 (6.4)

Btu/Hr (kw)

Total

= 62,000 (18.2)

Btu/Hr (kw)

C.Install a lower Btu/Hr (kw) heater, if lower Btu/Hr (kw) size makes room unconfined.

If the actual Btu/Hr (kw) used is less than the maxi- mum Btu/Hr (kw) the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

VENTILATION AIR WARNING:Iftheareainwhich the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" (30.5 cm) of the ceiling and one within 12" (30.5 cm) of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr (kw) the space can support with the actual amount of Btu/Hr (kw) used.

___________Btu/Hr (kw) (maximum the space can support)

___________Btu/Hr (kw) (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (15 kw) (maximum the space can support)

62,000 Btu/Hr (18.2 kw) (actual amount of Btu/Hr used)

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12" (30,48 cm)

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the above example is a confined space because the actual Btu/Hr (kw) used is more than the maximum Btu/Hr (kw) the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 7.

12" (30,48 cm)

Figure 2 - Ventilation Air from Inside

Building

6

www.desatech.com

113261-01C

Page 6
Image 6
Desa VTP22R, VTN25R Continued, Ventilation Air From Inside Building, Ventilation Air from Inside Building