Desa (V)V36P-B SERIES, VV36PC1 SERIES Horizontal Termination Configurations, Continued

Models: (V)V36P-B SERIES, VV36PC1 SERIES CHDV36NR-C (V)V36N-B SERIES, VV36NC1 SERIES

1 40
Download 40 pages 55.19 Kb
Page 10
Image 10
Recommended Applications:

10

VENTING INSTALLATION INSTRUCTIONS

Installation Planning (Cont.)

VENTING INSTALLATION INSTRUCTIONS

Continued

9.Combustible Exterior Wall Only: Slide wall firestop against interior wall surface and attach with screws provided. See Fig- ure 13 for horizontal termination details.

10.Place fireplace into position and shim with noncombustible ma- terial if needed. Nail or screw side flanges to framing to secure unit in place. IMPORTANT: Make sure fireplace is level before securing. If fireplace is not level it will not work properly.

•Installation using cabinet surrounds WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main- tained venting system could result in serious injury, property damage or loss of life.

GROUND FLOOR INSTALLATION

Recommended Applications:

Minimum Pipe

Overlap 11/4"

Direct Vent

Pipe

Wall

Firestop

Maintain 1"

Minimum Air

Space Around

Outer Pipe When

Penetrating a Wall

10 3/4" x 10 3/4"

Framed

Opening

Siding Standoff

Screws

•NOT FOR CORNER INSTALLATION High Wind

Termination

Apply Mastic to Outside Edge of Standoff

Exterior Wall with Vinyl Siding

Installation using cabinet surrounds

Through the wall using round or square termination (up to 12" horizontal pipe)

NOT FOR CORNER INSTALLATION

45° Elbow

Horizontal High

Wind Square

Termination

Adjustable

Pipe 12" Max.

Wall Firestop

 

 

Square Termination

 

Vertical (V)

Horizontal (H)

 

32 3/4" min.

17" max.

45° Elbow

Exterior Portion of Wall

 

Wall

Firestop (Round

Firestop

Termination Only)

Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding Standoff Installed

Horizontal Termination Configurations

Figures 14 through 18 show different configurations and alternatives for venting with horizontal termination. Each figure includes a chart with critical minimum and maximum dimensions which MUST be met. IMPORTANT: Remember that a horizontal run of venting must have a 1/4" rise for every 12" of run toward the termination.

NOTICE: Do not seal termination cap to vent pipe. Cap must be removable for vent inspection and maintenance.

Horizontal Termination Configurations Horizontal

Round

Termination

Figure 14 - Horizontal Termination Configuration for Square or Round Terminations

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundForManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background.Manual backgroundManual backgroundManual backgroundManual background.comManual backgroundManual backgroundManual backgroundManual backgroundManual background

111252-01E

Page 10
Image 10
Desa (V)V36P-B SERIES, VV36PC1 SERIES Horizontal Termination Configurations, Venting Installation Instructions, Continued

FAQ

What are the recommended applications for this indoor fireplace?

The recommended applications include minimum pipe overlap, direct vent pipe wall firestop, and maintaining minimum air space around the outer pipe when penetrating a wall.

Can this fireplace be installed using cabinet surrounds?

Yes, it can be installed through the wall using round or square termination up to 12" horizontal pipe, but it is not suitable for corner installation.

What are the different horizontal termination configurations for venting?

There are various configurations and alternatives for venting with horizontal termination, each with critical minimum and maximum dimensions that must be met.