Dimplex LIK 8MER 6.3Heating System Connection, 6.4Electrical Connection, Antifreeze, English

Models: LIK 8MER

1 26
Download 26 pages 26.11 Kb
Page 7
Image 7
6.3Heating System Connection

[

0[

The air outlet can be optionally mounted directly to a wall open- ing or to a longer duct (available as an accessory). Use the same mounting procedure as for the air inlet.

If a flange-mounted air duct is used on the air outlet side, it is se- cured with 4 M8 x 16 hexagon bolts in the threaded holes pro- vided. When doing this, ensure that the air duct stubs only touch the insulation. There should be no contact with the external sheeting.



0  [ 

PD[ 

PLQ



Observe the external and internal dimensions as specified in the figure. Also ensure that the vibration and duct isolation are ade- quate.

6.3Heating System Connection

To enable connection to the heating system, flexible hose con- nection pieces and double nipples with a 1" external thread are included with the heat pump. These allow the optional use of a threaded or flat gasket connection to the heating system.

If the heat pump is not intended to be used to heat up the hot wa- ter, the hot water output must be permanently sealed using the supplied sealing plug.

Before connecting the heating water system to the heat pump, the heating system must be flushed to remove any impurities, residue from sealants, etc. Any accumulation of deposits in the liquifier could cause the heat pump to completely break down.

6.4

 

An overflow valve is installed in the device for systems in which

 

the heating water flow can be shut off via the radiator or thermo-

 

stat valves. This ensures a minimum heating water flow rate

 

through the heat pump and helps to avoid faults.

 

Once the heating system has been installed, it must be filled, de-

 

aerated and pressure-tested.

 

The integrated expansion vessel has a volume of 24 litres. This

 

volume is suitable for buildings with a living space area to be

 

heated of maximum 200 m².

 

The volume should be checked by the heating system engineer.

 

If necessary, an additional expansion vessel must be installed

 

(according to DIN 4751, Part 1). The tables listed in the manufac-

English

turers' catalogues simplify dimensioning the system on the basis

of the water content. Allow for a buffer tank volume of 80 litres

 

when making the calculation.

 

ATTENTION!

In the case of large-volume heating circuits, an additional expansion vessel must be used to supplement the installed expansion vessel (24 litres, 1.0 bar admission pressure).

Antifreeze

A method of manual drainage (see illustration) should be pro- vided for heat pumps which are exposed to frost. The antifreeze function of the heat pump controller is active whenever the con- troller and the heat circulating pumps are ready for operation. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. The heating circuit should be operated with a suitable antifreeze if heat pump systems are implemented in buildings where a power failure can not be de- tected (holiday home).

6.4Electrical Connection

The power supply and control voltage are supplied using stand- ard cables (load: 3-core, control: 3-core).

A disconnecting device with a contact gap of at least 3 mm (e.g. utility blocking contactor or power contactor) as well as a 1-pole circuit breaker must be installed in the power supply by the cus- tomer (tripping current in compliance with the Device Informa- tion).

The control voltage must be protected by a 10 A fuse. See Ap- pendix Circuit Diagrams for detailed information.

www.dimplex.de

E-6

Page 7
Image 7
Dimplex LIK 8MER manual 6.3Heating System Connection, 6.4Electrical Connection, Antifreeze, English