7 - OUTPUT OPTIONS

7 - OUTPUT OPTIONS

7.1

OUTPUT OPTIONS

OUTPUT OPTIONS

7.2

BELL CUTOFF: 15

This function allows you to program the panel's Bell Output functions and certain Output options. Switched Ground (open collector) outputs are available from the XR10 when using a 4-wire output harness (Model 300 Harness). Refer to the XR10 Installation Guide (LT-0229) for complete information.

A description of each output option follows:

BELL CUTOFF TIME

Enter the maximum time the Bell Output remains on. If the Bell Output is manually silenced or the system is disarmed, the cutoff time is reset. The Bell Cutoff Time can be from 1 to 15 minutes in one minute increments.

Enter zero to provide a continuous bell output.

7.3

BELL TEST NO

AUTOMATIC BELL TEST

When YES is selected, the Bell Output is turned on for two seconds when all areas in the system are armed. In addition, the Closing Wait feature is activated if Opening/Closing Reports is YES. See section 5.2.

Closing Wait operation

Closing Wait provides a delay time before a monitored system arms until the panel receives an acknowledgment of the closing report from the central station receiver. During the delay, the keypad displays DIALING . . .. Once the closing is acknowledged, the keypad buzzer and the Bell Output sound for two seconds and the keypad displays the system armed message.

If the closing report is not acknowledged, the keypad buzzer and Bell Output do NOT sound, the keypad displays LOCAL ALARM ONLY, and the system arms locally.

7.4

7.4A

BELL ACTION . . . . .

FIRE

TYPE: P

 

 

BELL ACTION

This option defines the type of Bell Output for zone alarms. (Trouble conditions do not activate the Bell Output.) There are seven zone types you can program for Bell Output.

For a steady Bell Output, enter S. For a pulsed output, enter P. For no Bell Output, enter N.

Program the bell action for each zone type below:

FIRE ZONES

Defines Bell Action for Fire Type Zones.

7.4B

BURGLARY TYPE: S

BURGLARY ZONES

Defines Bell Action for Burglary Type zones. If you select N, Exit Error alarms are not indicated locally but Exit Error reports are still sent to the receiver. See Appendix section 11.2.

7.4C

SUPRVSRY TYPE: N

 

 

 

7.4D

PANIC

TYPE: N

 

 

7.4E

EMERGNCY TYPE: N

 

 

 

7.4F

AUXLRY I TYPE: N

7.4G

 

 

 

 

AUXLRY

2 TYPE: N

 

 

 

XR10 Programming Guide

SUPERVISORY ZONES

Defines Bell Action for Supervisory Type Zones

PANIC ZONES

Defines Bell Action for Panic Type Zones

EMERGENCY ZONES

Defines Bell Action for Emergency Type Zones

AUXILIARY 1 ZONES

Defines Bell Action for Auxiliary 1 Type Zones

AUXILIARY 2 ZONES

Defines Bell Action for Auxiliary 2 Type Zones