7 - OUTPUT OPTIONS
7.5
OUTPUT ACTION . . .
OUTPUT ACTION
This option allows you to define the operation of the panel's four annunciator outputs.
7.5A
CO OUTS: - - - -
CUTOFF OUTPUTS
7.5B CUTOFF TIME: 0
7.5C COM FAIL OUT: 0
7.5D FIRE ALR OUT: 0
7.5E FIRE TRB OUT: 0
7.5F AMBUSH OUT: 0
7.5G ENTRY OUT: 0
Any or all of the available outputs can be programmed here to turn off after the time specified in OUTPUT CUTOFF TIME. See section 7.5B. To disable this option, press any SELECT key to clear the display of output numbers and then press COMMAND.
OUTPUT CUTOFF TIME
If a Cutoff Output is assigned in section 7.5A, you can enter a Cutoff Time of up to 15 minutes for the output to remain on. If the output is turned off manually, the cutoff time is reset. The Cutoff Time can be from 1 to 15 minutes. Enter zero to provide continuous output.
The Cutoff Timer is shared by all outputs. If a second output trips, the timer is not reset. Both outputs turn off when the original time expires.
COMMUNICATION FAILURE OUTPUT
This output is turned on when a DD or
FIRE ALARM OUTPUT
This output is turned on any time a fire type zone is placed in alarm. The output is turned off using the Sensor Reset option while no additional fire type zones are in alarm. Enter zero to disable this output.
FIRE TROUBLE OUTPUT
This output is turned on any time a fire type zone is placed in trouble or when a supervisory type zone is placed in alarm or trouble. The output is turned off when all fire and supervisory type zones are restored to normal. Enter zero to disable this output.
AMBUSH OUTPUT
This output is turned on any time an Ambush code is entered at a keypad. The output is turned off using the Sensor Reset option. Enter zero to disable this output.
ENTRY OUTPUT
This output is turned on at the start of the entry delay time. The output is turned off when the area is disarmed or the entry delay time expires. Enter zero to disable this output.
7.5H
EXIT OUT: | 0 |
EXIT OUTPUT
7.5I
READY OUT: 0
This output is turned on any time an exit delay time starts. The output is turned off when the system arms or when the arming has been stopped. Enter zero to disable this output.
READY OUTPUT
This output is turned on whenever all disarmed zones are in a normal state. The output is turned off when any disarmed zone is in a bad state. Enter zero to disable this output.
7.5J
ARMED OUT: | 0 |
ARMED OUTPUT
7.5K BURGLARY OUT: 0
7.5L GROUND START: 0
This output is turned on any time an area of the system is armed. The output is turned off when the system is completely disarmed.
BURGLARY OUTPUT
This output turns on any time a burglary zone is in alarm. The output is turned off when the area in which the alarm occurred is disarmed and no other burglary zones are in alarm.
GROUND START OUTPUT
This output turns on for 750ms any time the panel seizes the telephone line. Enter zero to disable this output.
2841 E. Industrial Drive Springfield, MO