11 - APPENDIX
11.1Status List
The Status List is the current status of the system or records of recent system events that are displayed on the alphanumeric keypads. For example, in Home/Away systems, you might see the display SYSTEM READY. This would be the current status of the system.
If an event were to occur on the system, such as an AC failure, the keypad would also display the AC POWER - TRBL message. This is a system event that is placed into the Status List to alert the user to a problem with the system.
Some Status List items remain in the display until manually cleared and some are cleared automatically when the condition returns to normal. Below is a complete list of status and event displays the keypad can show in the Status List:
Description | Must be manually cleared? |
Fire and Supervisory zone alarms | Yes - by Sensor Reset |
Fire and Supervisory zone troubles | No - clears when zone restores |
Burglary zone alarms | No - clears after 8 minutes or at disarming. |
All other zone alarms | No - clears when zone restores |
Zone monitor displays | No - clears after 8 minutes |
Day zone alerts | No - clears after 8 minutes |
System monitor troubles | No - clears when condition restores |
(AC and battery trouble) |
|
Armed status display | No |
(System On) |
|
Disarmed status displays | No |
(System Ready, System Not Ready) |
|
Remote keypad messages | No |
(Sent to the keypad by your office or central station) |
|
Each item in the list is displayed for four seconds. When there are multiple items in the list, you can use the COMMAND or ARROW keys to scroll forward or back through the items.
11.2False Alarm Reduction Features
System Recently Armed report
The System Recently Armed report (S78) is sent when a burglary zone is placed into alarm within five minutes of the system being armed.
Exit Error report
The Exit Error report is sent when an Exit zone is in a bad condition at the end of the Exit Delay time.
11.34-2 reporting operation
When using the
1.The panel dials the receiver phone number and waits for a response.
2.If the panel detects it is communicating with a
3.If the panel detects it is communicating with a DMP
4.If the panel last communicated to a
5.If the panel last communicated to a DMP
XR10 Programming Guide
2841 E. Industrial Drive Springfield, MO
17