How to set the Recall Test time

3 - COMMUNICATION

3.6

TEST FREQ: 0

TEST FREQUENCY

Allows you to set how often the panel's test report is sent to the receiver. Enter from 1 to 60 days. Enter zero to disable the test report.

3.7RECEIVER 1 PROG

3.8

ALARM

YES

 

 

 

3.9

SPV/TRBL

YES

3.10

O/C USER

YES

 

 

 

3.11

TEST RPT

YES

 

 

 

3.12BACKUP NO

3.13FIRST PHONE NO.

3.14SECOND PHONE NO.

3.15RECEIVER 2 PROG

How to set the Recall Test time

Once you have finished programming the panel, reset the panel by shorting the J16 reset jumpers for two seconds. The Recall Test timer now begins and runs for twelve hours. After twelve hours has elapsed, the Recall Test is sent to the receiver. Whatever time of day this happens to be is the time that the Recall Test will always be sent according to the number of days you selected in Test Frequency.

RECEIVER 1 PROGRAMMING

Allows you to set the reporting options for the first receiver the XR10 panel attempts to contact when sending reports. The XR10 supports communication to two receivers.

ALARM REPORTS

Select YES to enable Abort, Alarm, Alarm Restoral, Ambush, Exit Error, and System Recently Armed reports to be sent to this receiver.

SUPERVISORY/TROUBLE REPORTS

Select YES to enable supervisory, trouble, trouble restoral, force armed, and zone fault reports to be sent to this receiver.

OPENING/CLOSING AND USER REPORTS

Select YES to enable opening/closing, door access, schedule and code changes, bypass, and zone reset reports by user to be sent to this receiver.

TEST REPORT

Select YES to enable the Recall Test report to be sent to this receiver. Reports are sent according to the programming in section 3.6.

BACKUP REPORTING

YES enables this receiver to be a backup to the other receiver in the event the other receiver cannot be contacted.

FIRST TELEPHONE NUMBER

This is the first number the panel dials when sending reports to this receiver. Phone numbers can be up to 15 characters in length. You can program a three second pause in the dialing sequence by entering the letter P. You can program a dial tone detect by entering the letter D. These characters are counted as part of the 15 allowable characters.

SECOND TELEPHONE NUMBER

The panel dials the second number when two successive tries using the first number have failed. If the panel cannot reach the receiver after two attempts using the second number, it returns to the first number and makes two additional attempts. A total of ten dialing attempts are made using the first and second phone numbers. If a second phone number is not entered, the first phone number is used for all dialing attempts.

Each number can be up to 15 characters in length including any P or D characters entered for pause and dial tone detect.

RECEIVER 2 PROGRAMMING

Repeat steps 3.7 through 3.14 when communicating to a second receiver. Receiver 2 defaults are set to NO.

If you select YES for any of the Receiver 2 options, you must have at least one phone number programmed in Receiver 2 programming.