7

3.0

Operation

 

 

This section describes:

 

 

The UPS front panel

Standby mode

Turning the UPS on and off

Diagnostic tests

• Starting the UPS on battery

3.1UPS Front Panel

The UPS front panel indicates the UPS status and also identifies potential power problems. Figure 6 shows the UPS front panel indicators and controls.

Figure 6. UPS Front Panel

NOTE If the alarm beeps or if the indicator is on, see Table 10 in Section 9.0 to identi- fy and correct the problem. To configure parameters through the front panel, see Section 4.0 "Configuration".

Display Mode

To view the UPS current settings, press the button for one second and release. Use the button to scroll through the list of settings, which appear in the following order:

LCD Message

Description

I/P VOLT= xxx.xV

Input voltage.

I/P FREQ= xx.xHZ

Input frequency.

O/P VOLT= xxx.xV

Output voltage.

O/P FREQ= xx.xHZ

Output frequency.

O/P Load = x%

Approximate percentage of UPS load capacity being used

 

by the protected equipment.

O/P Watt= xW

Output watts.

O/P VA= xVA

Output VA.

O/P Cur= x.xA

Output current.

BAT VOLT= xx.xV

Battery voltage.

BAT CHARGE= xxx%

Approximate percentage of battery capacity remaining.

BackUp Time= xxxM

Approximate battery time remaining in minutes. The display

 

changes to seconds after one minute (Backup Time= xxxS).

CPU Version x.xx

Firmware revision level.

NOTE The UPS exits Display mode automatically after five seconds if the button is not pressed. To lock the meter screen, press the button until a beep is heard (3 seconds) then release it. To unlock the display, press the button until a beep is heard, then release it.

Page 10
Image 10