11

Table 1. Configuration Mode Parameters (cont.)

Parameter

LCD Message

Description

Default Settings

Manual Battery Test

Manual Bat Test

To initiate a manual battery test, press the button

Battery Test

 

 

twice when “Manual Battery Test” is displayed on the

 

 

 

LCD. During the test the LCD displays ON BATTERY.

 

 

 

The UPS resets the automatic timer after a manual

 

 

 

battery test. The LCD displays “Battery not charged”

 

 

 

when UPS test is requested but the battery is not

 

 

 

fully charged.

 

Manual UPS Test

Manual UPS Test

To initiate a manual UPS self-test, press the button

UPS Test

 

 

twice. During the test, the LCD displays ON BATTERY.

 

Site Wiring Fault Alarm

Site Fault Set

Select Enable or Disable. When enabled, the alarm sounds

Detect Enable

 

 

when the ground connection is missing or the line and

 

 

 

neutral wires are reversed in the wall outlet.

 

Modem Support

Modem Support

This parameter is reserved for future use, and should not

No Modem Support

 

 

be modified by the user.

 

Number of Extended

Bat Pack Num Set

Select the number of EBMs connected to the UPS:

Extern Pack: 0

Battery Modules

 

• For 700-1500 VAmodels, select 0 through 2

 

 

 

• For 2000-3000 VAmodels, select 0 through 5.

 

 

 

You are prompted to save this setting. Refer to the

 

 

 

documentation that came with your battery pack for

 

 

 

more information.

 

Communications Lock-

COM Control

For greater levels of security, users may choose to have

Enable

out

Cmds

the UPS disregard shutdown commands that come from

 

 

 

the power management software or other communication

 

 

 

sources.

 

 

 

• When disabled, the UPS does not accept a shut down

 

 

 

command via the communication port, USB port, or

 

 

 

communication slot adapter.

 

 

 

• When enabled, the UPS operates normally in response

 

 

 

to external commands.

 

 

 

You are prompted to save this setting.

 

Load Segment Control

Load Group Set

Allows manual control of load segments (see “Load

Group 1On 2On

 

 

Segments” Section 5.3)

 

 

 

By repeatedly pressing the scroll button, the individual

 

 

 

load segments can be turned on and off.

 

 

 

CAUTION To prevent the unintentional shutdown of

 

 

 

specific load segments, confirm your selection before

 

 

 

pressing the button.

 

Manual Bypass

Manual Bypass

This parameter is used to manually place the UPS in

Bypass OFF

 

GO

Bypass mode.

 

Configuration Mode

Config Mode Set

This parameter is reserved for future use, and should not

EscapeConfigMode

Setting

 

be modified by the user. The setting may be toggled

 

 

 

between EscapeConfigMode and Enter ConfigMode. 5.0

 

 

 

It should always be set to EscapeConfigMode.

 

Page 14
Image 14
Eaton Electrical 9120 manual Configuration Mode Parameters