Eaton Electrical 9120 manual Configuration Mode Parameters

Models: 9120

1 32
Download 32 pages 54.76 Kb
Page 13
Image 13

10

Table 1. Configuration Mode Parameters

Parameter

LCD Message

Description

Default Settings

Output Voltage Setting

O/P V Setting

To change the output voltage

 

 

 

• Select 208, 220, 230, or 240V for 240V models.

For 240V models:

 

 

You are prompted to save this setting.

O/P V= 230V

 

 

 

 

Input Voltage Tolerance

I/P Bypass Set

Select the input voltage tolerance range before the UPS

I/P Tol=+10%/-15%

 

 

goes to Battery mode: ±10%, +10%/-15%, or +15%/-20%.

 

 

 

You are prompted to save this setting.

 

Input Frequency

I/P F Setting

The factory-default is 50 or 60 Hz, ±5%. Select ±2% for

Freq Tol.=+/-15%

 

 

a narrower frequency range. Select ±7% for a wider

 

 

 

frequency range.

 

 

 

You are prompted to save this setting.

 

High-Efficiency Mode

HE Mode Setting

Select whether High-Efficiency mode is On or Off. If

HE Mode Off

 

 

enabled, you must also select the input voltage range:

 

 

 

±10% or ±15%.

 

 

 

While operating in High-Efficiency mode, the UPS

 

 

 

transfers to utility power when: 1) the input voltage is

 

 

 

outside ±10% or ±15% from nominal; 2) the input

 

 

 

frequency is greater than ±3%; or 3) the input line is

 

 

 

not available.

 

 

 

You are prompted to save this setting. If the setting is

 

 

 

not allowed, the LCD shows “I/P out limit” which means

 

 

 

the input voltage or frequency is not suitable.

 

Free Run Mode

Free Run Mode

Select whether Free Run mode is On or Off. If enabled,

Free Run On

 

 

you must also select Bypass Disable or Bypass Enable.

(Bypass Disable)

 

 

This selection defines how your UPS runs when the input

 

 

 

frequency (from the utility) is outside the selected frequency

 

 

 

tolerance (set via the I/P F Setting, above), but is inside the

 

 

 

maximum frequency limits the UPS can accept before

 

switching to Battery mode.

For example: If your 50 Hz UPS is set to the factory default window of ±5% before the UPS starts regulating the frequency.

The output frequency tracks the input frequency exactly from 47.5 to 52.5 Hz.

If input frequency is between 45 and 65 Hz, the output frequency is regulated by the UPS to exactly 50 Hz (±0.5 Hz). You are prompted to save this setting.

Alarm Silence

Alarm Silence

Select whether Silence is On or Off. If enabled, the UPS

Silence Off

 

 

silences the alarm for an existing fault. If the UPS status

 

 

 

changes, the alarm beeps, overriding the previous alarm

 

 

 

silencing. The alarm does not silence if there is a low

 

 

 

battery condition.

 

Page 13
Image 13
Eaton Electrical 9120 manual Configuration Mode Parameters, Parameter LCD Message Description Default Settings