14

5.7Relay Card

This interface provides true relay contact output to peripheral devices. Outputs are user-selectable as normally open or normally closed.

Table 2. Relay Card (AS/400) Pin Assignment

 

Pin Number

Signal Name

Definition

 

Direction

 

1

-

Isolated common to pins 2 & 3

-

 

2

Line OK

Relay contact; closed to pin 1

-

 

3

Line Failure

Relay contact; closed to pin 1

-

 

4

-

Isolated common to pins 5 & 6

-

 

5

Battery Normal

Relay contact; closed to pin 4

-

 

6

Battery Low

Relay contact; closed to pin 4

-

 

7

-

Isolated common to pins 8 & 9

-

 

8

UPS Alarm

Relay contact; closed to pin 7

-

 

9

UPS On/OK

Relay contact; closed to pin 7

-

 

10

-

Isolated common to pins 11 & 12

-

 

11

UPS Online/Inverter

Relay contact; closed to pin 10

-

 

12

UPS on Bypass

Relay contact; closed to pin 10

-

 

13

+12VDC

Signal supply +12VDC

 

Out

 

14

Signal GND

Signal ground - Common

-

 

15

UPS Shutdown

Minimum 5 seconds high level

In

 

 

 

 

signal (+12VDC) to perform

 

 

 

 

 

shutdown according to following

 

 

 

 

 

Relay Card Jumper settings:

 

 

 

 

 

 

 

 

 

 

 

 

JP1 (default)

JP2

 

 

JP3

 

UPS Normal

 

-

No response

 

Go to bypass mode,

 

 

 

 

 

 

back online when

 

 

 

 

 

 

shutdown pins opened

 

 

 

 

 

 

 

 

UPS on Battery

 

Output off after

Immediate output off

 

Immediate output off

 

 

 

120 sec. Back online

UPS shutdown in

 

UPS shutdown in

 

 

 

on resumption of AC

12 seconds

 

12 seconds

 

 

 

power

 

 

 

 

 

 

 

 

 

 

 

 