Table 6. Environmental and Safety
240V Models
Operating Temperature 0°C to 40°C 0-1500 metres above sea level
0°C to 35°C 1500-3000 metres above sea level
Optimal battery performance: 25°C
Storage Temperature -15°C to 50°C
Relative Humidity 0-95% noncondensing
Operating Altitude Up to 3,000 metres above sea level
Audible Noise 700-1500 VA: Less than 48 dBANormal mode, typical load
2000-3000 VA: Less than 54 dBANormal mode, typical load
Surge Suppression ANSI/IEEE C62.41 (1991); ANSI/IEEE
C62.45 (1987) Category B
Safety Conformance AS/NZS 3260
EMC AS/NZS 2064, AS/NZS 3548, C-Tick Marked,
AS/NZS 61000-4-2, -3, -4, -5 Compliant
Table 7. Weights and Dimensions
UPS 240V Models
Dimensions
(WxDxH) 700-1000 VA: 15.8 x 41.2 x 24.3 cm
1500 VA: 17.0 x 44.4 x 27.5 cm
2000-3000 VA: 21.7 x 47.2 x 36.1 cm
Weight 700 VA: 12.6 kg
1000 VA: 15.3 kg
1500 VA: 19.8 kg
2000 VA: 37 kg
3000 VA: 38.5 kg