Installation Instructions

NOTE: If you need to install ducts, note that the total

Maximum duct length:

duct length of 3¼" x 10" rectangular or 6" diameter

For satisfactory air movement, the total duct length of

round duct should not exceed 140 equivalent feet.

3¼" x 10" rectangular or 6" diameter round duct

Outside ventilation requires a HOOD EXHAUST

should not exceed 140 equivalent feet.

DUCT. Read the following carefully.

Elbows, transitions, wall and roof

NOTE: It is important that venting be installed using

caps, etc., present additional resistance to

the most direct route and with as few elbows as

possible. This ensures clear venting of exhaust and

airflow and are equivalent to a section of straight duct

which is longer than their actual physical size. When

helps prevent blockages. Also, make sure dampers

calculating the total duct length, add the equivalent

swing freely and nothing is blocking the ducts.

lengths of all transitions and adaptors plus the length

Exhaust connection:

of all straight duct sections. The chart below shows

The hood exhaust has been designed to mate with a

you how to calculate total equivalent ductwork length

standard 3¼" x 10" rectangular duct.

using the approximate feet of equivalent length of

If a round duct is required, a rectangular-to-round

some typical ducts.

transition adaptor must be used. Do not use less than a 6" diameter duct.

DUCT PIECES

EQUIVALENT

 

NUMBER

 

EQUIVALENT

 

LENGTH

x

USED

=

LENGTH

Rectangular-to-Round

 

 

 

 

 

 

Transition Adaptor*

5 Ft.

x

(

)

=

Ft.

Wall Cap

40 Ft.

x

(

)

=

Ft.

90° Elbow

10 Ft.

x

(

)

=

Ft.

45° Elbow

5 Ft.

x

(

)

=

Ft.

90° Elbow

25 Ft.

x

(

)

=

Ft.

45° Elbow

5 Ft.

x

(

)

=

Ft.

Roof Cap

24 Ft.

x

(

)

=

Ft.

Straight Duct 6" Round or

 

 

 

 

 

 

3¼" x 10" Rectangular

1 Ft.

x

(

)

=

Ft.

Total Ductwork

=

Ft.

*IMPORTANT: If a rectangular-to- round transition adaptor is used, the bottom corners of the damper will have to be cut to fit, using the tin

snips, in order to allow free movement of the damper.

Equivalent lengths of duct pieces are based on actual tests and reflect requirements for good venting performance with any vent hood.